OnOff Controller Installation (Continued)
Setting up the installation option of Indoor
Unit and OnOff Controller
1
Set the Indoor Unit installation option SEG5 to “1”.
It means use the OnOff controller.
2
Set the RMC(1) and RMC(2) address of Indoor Unit.
Example) RMC(1) = SEG11 = 0~F, RMC(2) = SEG12 = 0~F
However, when RMC(1) = F, RMC(2) can be set between 0~E
In Case of Installing OnOff Controller Only
OnOff Controller
You must reset the OnOff controller to apply the changed
RMC(1) address.
SW22
SW21
SW22
SW21
DIP Switch
RMC(1) address
(SW01) = 0~F
Cooling/Heating switch
Cooling
Heating
OFF : Left
ON : Right