Flow Sensor
Supplied with the Pre Plumbed cylinder is a Flow Sensor and a Flow Meter.
The Flow Sensor should be mounted within 2 M of the Control Kit.
This lead can be extended, it is a 4 core cable, if you do extend ensure that the cores are not
crossed.
The switch must be located indoors as it is only splash proof.
Ideally the Flow Switch will be mounted horizontally in the return line to the Outdoor unit.
The Switch must have a minimum of 300 mm of straight pipe either side of it.
The flow Switch plugs directly onto the MIM unit on Connections CSN 057