Error Mode
MASTER ERV Tracking error
Display
Check Method
Slave ERV check is not conducted when Tracking is carried out 5 times.
Cause
Option setup, PCB check or replacement
Sensor SPEC.
Non-polar communication
12-4-5 MASTER ERV Tracking Error
Yes
Check whether PCB address setup
is overlapped or not after having found
out SLAVE reporting error about
2 minutes later. (If PCB address setup
is overlapped, communication error
may occur.) In this case, both Slaves
with wrong address setup suffer from
communication error.
No
아니오
Does Tracking display show
no response at all from any Slave?
Check the communication
line of MASTER PCB and
connector, then, replace the PCB.
No
E201 code appears when unit
operation starts or while it is in operation.
Check display with pressing RESET KEY K3 of
MASTER PCB in order to CHECK number of Slaves
responding to Tracking.
After eliminate communication line
connecting Master and Slave, check the 2 lines
of Masterwith Scope.
Reconnect communication line between Mster
and Slave. Eliminate all communication connectors
on Slave PCB and connect them again one by one.
Find out the Slave interrupting communication
and check its lines. Then, replace Slave PCB.
If there is nothing wrong with address.
Check communication line and replace
Slave PCB.
Yes
Yes
+0.7V
-0.7V
Good
Bad
Is the voltage between the 2 lines
is square wave higher than DC±0.7V as
seen in the picture below?
Troubleshooting
27723A(1)_RHF-025EB_1.indd 7
2007-05-09 ソタネト 4:24:15
Содержание ERV RHF025EE
Страница 54: ...MEMO Samsung Electronics 5 6 27723A 1 _RHF 025EB_1 indd 41 2007 05 09 ソタネト 4 23 34 ...
Страница 99: ...MEMO Samsung Electronics 9 5 27723A 1 _RHF 025EB_1 indd 89 2007 05 09 ソタネト 4 24 08 ...
Страница 123: ...MEMO Samsung Electronics 12 17 27723A 1 _RHF 025EB_1 indd 17 2007 05 09 ソタネト 4 24 17 ...