Equivalent length calculation method
3/8”
1/2”
5/8”
3/4”
7/8”
1”
1 1/8”
1 1/4”
0.18
0.20
0.25
0.35
0.40
0.45
0.50
0.55
1.3
1.5
2.0
2.4
3.0
3.4
3.7
4.0
Piping diameter
Type
Elbow
Oil Trap
equivalent length = actual pipe number of number of elbows X equivalent length of each elbows
+ number of oil traps X equivalent length of each oil trap
Effective equivalent length = equivalent length of main piping X 0.5 + equivalent length after the by path
(when the diameter of gas pipe of the main piping is uplifted a level)
●
Application of equivalent length
1. When the equivalent length is more than 90% of the actually allowed piping length (more than
207ft. in five/six horse powers, 295ft. in seven/eight/ten horse powers, the gas pipe
diameter of the main piping (piping from the outdoor unit to the first bypass) is expanded a level.
For instance, when the equivalent length of 10 horse power outdoor unit is more than 328ft., the
gas pipe diameter is changed to 1 1/4” from 1 1/8”.
2. When the diameter of gas pipes is uplifted one level, the effective equivalent length is
recalculated, and the piping length is calculated based on the effective equivalent length
when looking into the graph to calculate the performance reduction by the long piping.
◆
Examples of equivalent length calculation : When 10 horse power outdoor unit’s actual length is 262ft.,
the piping diameter is 1”, twelve elbows and two traps are used,
the
equivalent length is 262+0.45X12+3.4X2 = 274.2(ft.)
◆
Examples of effective equivalent length calculation : When the actual length of 10 horse power outdoor unit is 262ft.,
piping after bypass 65ft., the diameter of gas pipe
of the main piping is 1”, twelve elbows and two oil traps
are used (elbows and oil traps are used only in main piping).
①
Equivalent length = 262+0.45X12+3.4X2=274.2(ft.)
➁
As the equivalent length is more than 295ft., the
diameter of gas pipe in the main piping is uplifted one level.
➂
Effective equivalent length = (262+0.45X12+3.4X2)X0.5+65=169.7(ft.)
➃
The performance loss due to the long piping is the same with
equivalent length of 169.7ft. when the diameter of gas pipes
of the main piping is not uplifted one level.
43
Λ
5-2.Installation_TM_E_06890 2/27/03 10:16 AM Page 43
Содержание Electronics DVM Series
Страница 3: ...1 Overview_TM_E_06890 2 27 03 10 11 AM Page 2 ...
Страница 4: ...SAMSUNG ELECTRONICS SAMSUNG DV MT M Air Conditioner 1 Overview_TM_E_06890 2 27 03 10 12 AM Page 3 ...
Страница 58: ...ΙΙ 33 8 Integrating power distribution system 2 Control system_TM_E_06890 2 27 03 10 13 AM Page 33 ...
Страница 59: ...ΙΙ Control System 9 Building management system ΙΙ 34 2 Control system_TM_E_06890 2 27 03 10 13 AM Page 34 ...
Страница 107: ...ΙΙΙ Indoor unit 7 Electric circuit diagram ΙΙΙ 48 2 Heat pump AVMKH 3 2 Indoor unit_TM_E_06890 2 27 03 10 14 AM Page 48 ...
Страница 108: ...ΙΙΙ 49 7 2 4 way cassette type 1 Cooling only AVMCC 3 2 Indoor unit_TM_E_06890 2 27 03 10 14 AM Page 49 ...
Страница 109: ...ΙΙΙ Indoor unit 7 Electric circuit diagram ΙΙΙ 50 2 Heat pump AVMCH 3 2 Indoor unit_TM_E_06890 2 27 03 10 14 AM Page 50 ...
Страница 110: ...ΙΙΙ 51 7 3 Duct type 1 Cooling only AVMDC AVMBC AVMHC 3 2 Indoor unit_TM_E_06890 2 27 03 10 14 AM Page 51 ...
Страница 112: ...ΙΙΙ 53 7 4 Wall mounted type 1 Cooling only AVMWC 3 2 Indoor unit_TM_E_06890 2 27 03 10 14 AM Page 53 ...
Страница 113: ...ΙΙΙ Indoor unit 7 Electric circuit diagram ΙΙΙ 54 2 Heat pump AVMWH 3 3 Indoor unit_TM_E_06890 2 27 03 10 14 AM Page 54 ...
Страница 164: ...7 Electric circuit diagram 26 Outdoor unit ΙΛ ΙΛ 2 070 4 2 Outdoor unit_TM_E_06890 2 27 03 10 15 AM Page 26 ...
Страница 165: ...27 ΙΛ 3 100 4 2 Outdoor unit_TM_E_06890 2 27 03 10 15 AM Page 27 ...
Страница 167: ...29 ΙΛ 2 100 4 2 Outdoor unit_TM_E_06890 2 27 03 10 15 AM Page 29 ...