Wiring work
f
Decide the power cable specification and maximum length within 10 % power drop among indoor units.
n
Coef×35.6×Lk×ik
10 % of input voltage[V]
∑(
) <
1000×Ak
k=1
• coef : 1.55
• Lk : Distance among each indoor unit[m], Ak : Power cable specification[mm
2
(inch
2
)], ik : Running current of each unit[A]
Example of Installation
f
Total power cable length L = 100 m(328 ft), Running current of each units 1[A]
f
Total 10 indoor units were installed.
10[A]
Indoor unit 10
20[m](65.62 ft)
10[m](32.8 ft)
0[m]
9[A]
1[A]
100[m](328 ft)
Indoor unit 2
Indoor unit 1
ELCB
Or MCCB+
ELB
f
Apply following equation.
n
Coef×35.6×L
K
×i
K
10 % of input voltage[V]
∑
(
) <
1000×A
K
k=1
❋
Calculation
• Installing with 1 sort wire.
220[V]
-2.2[V]
-2.0[V]
············ 2.5[mm
2
](0.004 inch
2
) ············
208.8[V](Within 187 V ~ 253 V)
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2[V]
it's okay
2.5[mm
2
](0.004 inch
2
)
2.5[mm
2
](0.004 inch
2
)
• Installing with 2 different sort wire.
220[V]
-1.4[V]
-1.2[V]
············ 2.5[mm
2
](0.004 inch
2
) ············
209.5[V](Within 187 V ~ 253 V)
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5[V]
it's okay
4.0[mm
2
](0.006 inch
2
)
4.0[mm
2
](0.006 inch
2
)
How to connect your extended power cables
1. Prepare the following tools.
Tools
Crimping pliers
Connection sleeve (mm)
Insulation tape
Contraction tube (mm)
Spec
MH-14
20xØ6.5(HxOD)
Width 19mm
70xØ8.0(LxOD)
Shape