Connecting centralized controller and DMS2 (
type)
- You can control up to 16 centralized controllers and 256 indoor units using DMS2.
Connecting interface module and DMS2(
type)
- You can control up to 80 interface modules and 256 indoor units using DMS2.
*16 interface modules can be connected to RS485 communication channel of DMS2.
- The more interface modules are connected, the longer time takes for tracking.
Display Board
40-pin Cable
20-pin Cable
DI contact control
option switch
Main Board
Sub Board
System Architecture
S-NET mini
Centralized
controller
DMS2
Internet
S-NET3
Interface module
Interface module
Interface module
When connecting centralized controller and interface module to the DMS2 of same
communication channel, only one of them will communicate according to the
communication channel mode setting of [System Settings]-[Tracking]. Therefore,
do not connect the centralized controller and interface module to the same
communication channel.
If you set the communication channel mode as interface module, virtual centralized
controller address will be assigned. Therefore please aware of that if you set the
centralized controller address as virtual centralized controller address when you
connect interface module and centralized controller at the same, it may cause trouble
for bringing device information.
Channel 0: Virtual centralized controller 11, Channel 1: Virtual centralized controller 12,
Channel 2: Virtual centralized controller 13, Channel 4: Virtual centralized controller 14,
Channel 5: Virtual centralized controller 15