E-
12
Connecting the Connection Cord (Continued)
1(L)
2(N)
Vc
Vc
Vw
Vw
F1
F2
V1
V2
F3
F4
F1
F2
Receiver &
Display Unit
(Optional)
Float Switch
Drain Pump
(Optional)
Wired
Remote
Controller
MAIN PCB
3
ø
220V~, 60H
z
Communication
Power
The following electrical characteristics must be respected.
MODEL
Power
Circuit breaker
Indoor unit power cable
Communication cable
Wired remote controller power
& communication cable
Power cable
20m or less
50m or less
DH48FTA(X), DH60FTA(X), DC48FTA(X), DC60FTA(X)
3ø 220V~, 60Hz
30A
1.25mm
2
(CV, 3 wire)
0.75~1.0mm
2
(CV, 2 wire)
The power cables are not
supplied with the air
conditioner.
The user should purchase
them separately.
0.5~0.75mm
2
(CV, 2 wire)
5.5mm
2
(CV, 4 wire)
8.0mm
2
(CV, 4 wire)
Note
MAIN POWER
Indoor Unit
Outdoor Unit
Wiring Diagram (DH48FTA, DH60FTA, DC48FTA, DC60FTA )
Cable Specifications