5-3 Sequence for trouble diagnosis
5-3-1 Outdoor temp. sensor(OPEN/SHORT)
Reoperation
after connect to
connector PCB
Yes
Outdoor unit thermistor
is defective(replace)
No
PCB and sensor are normal.
To perform the test
operation by use of K2
Outdoor unit display
Indoor unit display
How to determine
Reason of error
Er
→
t1 (Outdoor temp. sensor OPEN/SHORT error)
(Operation)
(Timer)
(Airflow)
(Filter)
Disconnection and short of outdoor temp. sensor
Disconnection or leak of applied sensor
Yes
No
Yes
Check the out temp.
sensor is normal or not by use of
out data display part
➞
Check the temp. data is
normal or not after pressing K4 3 times.
At this time, is occurred the difference
between the out temp. and data?
Reoperation after PCB replacement
Does the out temperature
sensor connected to PCB?
(CN41)
At this time, Is largely
deviate the resistance value from side
table value?
Temp.
(˚C)
70
60
50
40
30
20
10
0
-10
Resistance
(k
Ω
)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Measure the resistance value
between two terminals after
separating the out temp. sensor
connector from PCB
No
Samsung Electronics
24
DB98_22254A(1)_1 05/2/21 11:05 PM Page 24
Содержание DH094EAM
Страница 4: ...3 Samsung Electronics 1 2 1 Indoor Unit 1 2 Dimensions Unit mm...
Страница 5: ...Samsung Electronics 4 Product Specifications 1 2 2 Outdoor Unit Unit mm 880 310 798...
Страница 39: ...Samsung Electronics 38 9 2 Outdoor Unit This Document can not be used without Samsung s authorization...
Страница 40: ...MEMO 39 Samsung Electronics...
Страница 41: ...MEMO Samsung Electronics 40...