19
ENGLISH
Connecting the connection cord
The indoor unit is powered by the outdoor unit by means of a H07 RN-F
connection cable (or a more power model), with insulation in synthetic rubber
and jacket in polychloroprene(neoprene), in accordance with the requirements
of standard EN 60335-2-40.
1
Remove the screw on the electrical component box and remove the cover plate.
2
Route the connection cord through the side of the indoor unit and connect
the cable to terminals; refer to the figure below.
3
Route the other end of the cable to the outdoor unit through the ceiling &
the hole on the wall.
4
Reassemble the electrical component box cover, carefully tightening the screw.
Always remember to connect the refrigerant pipes before performing the electric connections.
When disconnecting the system, always disconnect the electric cables before disconnecting the refrigerant pipes.
Always remember to connect the air conditioner to the grounding system before performing
the electric connections.
CAUTION
1(L)
2(N) Vc Vc Vw Vw
F1 F2 V1 V2 F3 F4
Wiring diagram
Indoor unit
Outdoor unit
Wired
Remote
Controller
Main Power
220-240V~, 50Hz
EH035/052/070EAV1
DH052/070EAS
DH052/070EAV1
Between Indoor and Outdoor Connection Cord Specifications
Power Supply (Single Phase)
Earth Cable Communication Cable Home server
Power Supply
Max/Min(V) Connection Wire
220-240V~/50Hz
±
10%
1.25mm
2
Ø 1.6mm,1 wire
0.75~1.25mm
2
2 wires
0.75~1.25mm
2
2 wires
The terminal block designs and shape are subject to change according to the model.
For connection cord, use the grade H07RN-F or H05RN-F materials.
Screws on terminal block must not be unscrewed with the torque less than 12 kgf•cm.