Drainpipe and drain hose installation
Care must be taken when installing the drainpipe and drain hose for the
indoor unit so that condensate water is drained correctly outside.
1
Fix the flexible hose to the drainpipe.
The connection port of the flexible hose and PVC drainpipe must be fixed
with PVC adhesives.
Check out that the connected part doesn’t leak.
2
Connect the flexible hose to the flexible hose port.
Make sure that a rubber ring is installed on the drain hose port.
3
Install the drainpipe as shortly as possible.
Give a slightly slant to the drainpipe for proper drainage of condensate
water.
There must be no gap on the connected part so that the drainpipe is not
separated from the flexible hose .
4
Insulate the drainpipe, and then fix it as indicated.
Drain pipe
Flexible hose
Drain hose port
Indoor
unit
Band
Insulation cover band
Insulation drainpipe
Insulation cover drain
Band(Not supplied)
Adhesives
Band
Drain hose
Flexible
hose
Drain
hose
port
If a concentrated drain hose is installed, refer to the figure below.
Max. allowable axis gap
Max 0.787inch(20mm)
Indoor
Unit
Flexible hose Installation
Be horizontal
Indoor
Unit
Flexible hose
Max. allowable bending angle
Max. 30˚
Indoor
Unit
Centralized Drainage
1
Install main air vent at the front of the farthest indoor unit from the main
drain when installed indoor units are more than 3.
2
You may need to install individual air vent to prevent water flow back at the
top of each indoor unit drainpipe.
Hanger
Main drainpipe
Individual
air vent
Main air vent
Centralized horizontal drainpipe
(more than 1/100 slope)
21.7inch(550mm)