Additional Functions
E-
16
Compensation for lost temperature in heating operation
◆
Reduces the difference between an actual room temperature and a sensed
temperature by the air conditioner when heating.
Adjusting filter cleaning cycle
◆
You can adjust the cycle for filter sign indicator.
K5 K6 K7 K8
SW04
K5 K6 K7 K8
SW04
K5
2°C compensation
5°C compensation
Switch No.
Switch ON
Switch OFF
Control of electronic expansion valve at the indoor unit off
◆
When an indoor unit off makes refrigerant noise, set K11 to OFF position to
reduce the noise. However, if a distributor kit is installed, K11 must be at ON
position.
K9 K10 K11 K12
SW05
K11
Electronic expansion valve
step 80
Electronic expansion valve
step 0 (Sub cool control)
Switch No.
Switch ON
Switch OFF
K6
1000 hours
2000 hours
Switch No.
Switch ON
Switch OFF