Fixing the installation plate

The following connection accessories are optional. If they are not supplied, you should obtain them before installing the air 
conditioner.

Optional accessories

Insulated  

Assembly Pipe,  

Ø6.35mm   

 (1) 

Insulated Assembly 

Pipe, Ø9.52mm 

   (1)

✴✴

09

✴✴

Insulated Assembly Pipe, 

Ø12.70mm   (1) 

✴✴

12/18/19

✴✴

Insulated Assembly Pipe, 

Ø15.88mm  (1) 

✴✴

24/25

✴✴

PE T3 Foam Tube 

Insulation (1)

Vinyl Tapes (2)

Drain Plug (1)

Rubber Legs (4)

Pipe Clamps A (3)

Pipe Clamps B (3)

Cement Nails (6) 

M4 x 25 Tapped 

Screws (6)

Drain Hose,  

length 2m (1)

Putty 100g (1)

t

  If these accessories are supplied, they will be in the accessory box.

B

A

D

C

D

You can select the direction of the drain hose depending on where you want to 
install the indoor unit. Therefore before  xing the installation plate to a wall or a 
window frame, you must determine the position of the 65mm hole through which 
the cable, pipe and hose pass to connect the indoor unit to the outdoor unit. 
When facing the wall, the pipe and cable can be connected from the: 

 

!

 

Right (A)

 

!

 

Left (B)

 

!

 

Underside_right (C)

 

!

 

Rear_right or left (D)

1

Determine the position of the pipe and drain hose hole as seen in the picture 
and drill the hole with an inner diameter of 65mm so that it slants slightly 
downwards. 

CAUTION

   Make sure to drill only one hole after choosing the direction of 

the pipe. 

2

Fix the indoor unit.

If y

x the indoor unit on a wall

(1) Fix the installation plate to the wall giving attention to the weight of the 

indoor unit. 

Note

 

 If you mount the plate to a concrete wall using plastic 
anchors, make sure that gaps between the wall and the plate, 
created by projected anchor, is less than 20mm. 

Wall

<20mm

Plastic Anchor

If y

x the indoor unit on a window frame

(1) Determine the positions of the wooden uprights to be attached to the 

window frame. 

(2) Attach the wooden uprights to the window frame giving attention to 

the weight of the indoor unit.

(3) Attach the installation plate to the wooden upright using tapping 

screws.

Direction of pipe

120

7

2

68

7

2

(Unit : mm)

Pipe hole 
(Ø65mm)

t

  Fix the installation plate without inclining to one side.

t

   Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not 

strong enough to withstand the product weight, the unit could fall and cause injury.

09/12

✴✴

✴✴

170

7

2

85

7

2

(Unit : mm)

Pipe hole 
(Ø65mm)

**18/19/24/25**

Содержание AS09E Series

Страница 1: ...09E Series AQ12E Series AQ18E Series AQ24E Series AF SD Series Air Conditioner user installation manual imaginethe possibilities ThankyouforpurchasingthisSamsungproduct To receive more complete servic...

Страница 2: ...drain hose 32 33 Purging the connected pipes 34 Performing the gas leak tests 36 Fixing the indoor unit in place 37 Fixing the outdoor unit in place 37 Final check and trial operation 38 38 Pump down...

Страница 3: ...direct sunlight and water rain drops Do not install this appliance in a location where gas may leak u This may result in electric shock or fire Never install the outdoor unit in a location such as on...

Страница 4: ...so may result in electric shock or fire In the event of a gas leak such as propane gas LP gas etc ventilate immediately without touching the power plug Do not touch the appliance or power cord u Do no...

Страница 5: ...problems with the product Do not drink the water from the air conditioner u The water may be harmful to humans Do not apply a strong impact to the remote controller and do not disassemble the remote c...

Страница 6: ...doorhumidity Cooling Relative humidity 80 or less Dry Heating 27 C or less 5 C 24 C Internal protections via the unit control system u This internal protection operates if an internal fault occurs in...

Страница 7: ...the name ofthe parts Room temperature sensor Air intake up and down lay Disp spi Operation indicator Temperature indicator Timer indicator Remote control receiver Power button Smart Saver indicator Fi...

Страница 8: ...g modes see pages 10 11 for instructions Auto Clean Auto clean function Dry inside of the indoor unit to get rid of odor Temp Increase Decrease the temperature by 1 C OnTim The Temp Humi function is n...

Страница 9: ...attery changing time When the battery is exhausted will be displayed in the remote controller display When the icon appears change the batteries The remote controller requires two 1 5V AAA type batter...

Страница 10: ...ture and the fan speed to feel cooler in hot season t If current outside temperaturesare much higher than the selected indoor temperature it may take time to bring the inner temperature to the desired...

Страница 11: ...e cooling mode ir can be adjusted manually see page 12 for instructions Auto Auto Cool Auto Low Med High Dry Auto Fan Low Med High Heat Auto Low Med High Auto You can adjust the desired temperature by...

Страница 12: ...ction for 30 minutes position you prefer t Be extremely careful with your while adjusting the Horizontal There is a potential risk of personal injury when the unit is mishandled Using theTurbo functio...

Страница 13: ...or long because the default is set to 8 hour operation t If the mode is set less than 4 hours the operation will stop at the same time If the mode is set over 5 hours it will run asWake up stage from...

Страница 14: ...in 10 seconds after selecting the time the air indicator on the indoor unit AdditionaloptionsavailableinOntimermode You can select from Auto Cool Dry Fan H a e t Heat model AQ series Heat model AQ ser...

Страница 15: ...mode t When Smart Saver function is activated temperature range will be limited to 24 C 30 C t If the desired temperature is lower than 24 C turn the Smart Saver function by pressing theSmartSaver bu...

Страница 16: ...uns after stopping the air conditioner operation u The Auto clean indicator C1 on the indoor unit display appears and the Auto cleaning function runs Whentheairconditioneristurnedon u The Auto clean i...

Страница 17: ...d pull it down to open Then slightly lift the panel up t Do not clean the display using alkaline detergent t Do not use Benzene Thinner or CloroxTM They may damage the surface of the air conditioner a...

Страница 18: ...lter clean reminder is on please press FILTER RESET button on remote controller t If the Air dries in a or humid area odors may generate If it occurs re clean and dry it in a well ventilated area Open...

Страница 19: ...art to maintain the air conditioner properly Type Description Every2 weeks Every3 months Every4 months Onceayear Indoor unit 1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Cl...

Страница 20: ...he air conditioner operates in De ice mode automatically In De ice mode indoor fan stops and cool air does not come out t If the doors or windows are open it may cause bad cooling heating performance...

Страница 21: ...generated t Depending on the status of the air conditioner usage noise can be heard when refrigerant Smoke is generated from the outdoor unit t If may not be a but it can be a steam generatedby the de...

Страница 22: ...requirements set forth in the Operating limits table included in the manual shall immediately invalidate the warranty u The air conditioner should be used only for the applications for which it has be...

Страница 23: ...ther for people or things For this reason where it is not observed as indicated into the Installation Manual the cost necessary to reach and repair the won t be considered in warranty and charged to e...

Страница 24: ...engths as seenin the picture below when installing the air conditioner t Avoid the following places to preventmalfunction of the unit Where there is machine oil Salty environment such as seaside areas...

Страница 25: ...e upper part of the outdoor unit and the air outlet is towards the wall 500 or more 300 or more The upper part of the outdoor unit and the air outlet is opposite the wall When the walls are blocking f...

Страница 26: ...the air conditioner Installation Plate 1 18 19 24 25 09 12 Installation Plate 1 Batteries for Remote Control 2 Assy Instruction Manual Accessories in the Indoor Unit Case 3 wire Assembly Cable 1 Assem...

Страница 27: ...pe and drain hose hole as seen in the picture and drill the hole with an inner diameter of 65mm so that it slants slightly downwards CAUTION Make sure to drill only one hole after choosing the directi...

Страница 28: ...cable is 15 09 12 18 19 20 24 25 meters Electrical work 1 For electrical and earth works comply with the technical standards of electrical installations and the 2 Tighten the terminal block screw to u...

Страница 29: ...ow GroundWire Green Yellow AS24 25 AQ09 12 18 AQ24 Indoor unit Outdoor unit Ground wire Green Yellow Ground wire Green Yellow Indoor unit Outdoor unit Ground wire Green Yellow Ground wire Green Yellow...

Страница 30: ...operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used t The smaller one is forthe liquid refrigerant t The...

Страница 31: ...Shorten up to see page 24 If you need a pipe longer than 5 meters t You must extendthe assemblycable t You must add refrigerant to the pipes otherwise the indoor unit may freeze Unscrew the caps Pipes...

Страница 32: ...le t Tightenthe nut with torque wrench according to method Installingandconnectingthedrainhoseoftheindoorunit When installing the drain hose for the indoor unit check if condensation draining is adequ...

Страница 33: ...cessary 1 Detach the rubbercap with the plier 2 Detach the drain hose by pulling it and turningto the left 3 hose and the outlet ofthe drain pan 4 Attach the rubbercap with a screwdriver by turning it...

Страница 34: ...ntake To avoid this incident install a frame that is higher than estimated snow fall In addition install a snow proof hood to avoid snow from piling on the outdoor unit t When installing make sure the...

Страница 35: ...uts andthe service port cap to thevalve and tighten themat the torque of 183kgftcmwith a torque wrench 8 Checkfor a gas leak paying particular attention to the 3 way valve s stem nuts and to the servi...

Страница 36: ...opening valves check leaks using a leak detector for refrigerant Pump down before disconnecting therefrigerant connections for unit repair removal or disposal Pump down is an operation intended to co...

Страница 37: ...he discharged air out properly 2 Fix theoutdoor unit in level to an appropriate support using anchor bolts 3 If the outdoor unitis exposedto strong winds install shield plates around the outdoor unit...

Страница 38: ...s after close thevalve on the low pressure side 5 Stop operation of theair conditioner 6 Disconnect the pipes 3 Press theAir swing button and checkthefollowing u 4 Press thePower button to stop the op...

Страница 39: ...your contraction tube in the middle ofthe insulation tape 5 Apply heat to the contraction tubeto contract it 6 After tubecontraction workis completed wrap it with the Tools Crimping plier Connections...

Страница 40: ...6 7864 www samsung com QATAR 4450 4533 www techno blue com BAHRAIN 8000 4726 www samsung com m o c g n u s m a s w w w 800 SAMSUNG 726 7864 OMAN m o c g n u s m a s w w w 0800 22273 JORDAN EGYPT 08000...

Отзывы: