Step 2.3 Connecting the power and
communication cables (assembly
cable)
Control box
1(L)2(N)
F1 F2
•
When performing electrical and earthing works,
be sure to comply with the 'technical standards of
electrical installations' and the 'wiring regulations' in
the local regulations.
• Tighten the terminal block screw to 1.2-1.8 N•m (1.2-
1.8 kgf•cm).
NOTE
•
Each wire is labelled with the corresponding terminal
number.
•
Use shield cable (Category 5; less than 50pF/m) for
noisy environmental site.
•
Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC: 60227
IEC53/CENELEC: H05VV-F, IEC: 60245 IEC 66/
CENELEC: H07RN-F, IEC: 60245 IEC 57/CENELEC:
H05RN-F)
•
Power & Communication cable shall not exceed 30m.
CAUTION
•
For the terminal block wiring, use a wire with a
ring terminal socket only. Regular wires without
a ring terminal socket may become a hazard due
to overheating of the electrical contact during
installation.
•
If you need to extend the pipe, be sure to extend
the cable, too. The maximum length of each of the
cable and pipe used should not exceed 15 metres
(
✴✴
09/10/12/13
✴✴
), 20 metres(
✴✴
18/24
✴✴
ME/UN)
and 30 metres(
✴✴
18/24
✴✴
SS/TC).
•
Do not connect two or more different cables to
extend the length. This connection may cause fire.
•
Each circular terminal must match the size of its
corresponding screw in the terminal block.
•
After connecting the cables, make sure that terminal
numbers on the indoor and outdoor units match.
•
Ensure that power and communication cables are
separated, they must not be in the same cable.
WARNING
•
Connect the wires firmly so that wires cannot be
pulled out easily. (If they are loose, it could cause
burn-out of the wires.)
Before
connecting
Correct
Upside down
Damaged
Non-circular
After
connecting
Correct
Correct
Upside down
Non-fitted
(Front view)
(Side view)
<Circular terminal>
Model
✴✴
09/12
✴✴
ME/TC
✴✴
10/13
✴✴
UN
✴✴
18
✴✴
ME/UN
✴✴
24
✴✴
ME/UN
Power cable
(Indoor unit)
3G X 1.0 mm²,
H05VV-F
3G X 1.5 mm²,
H05VV-F
3G X 2.5 mm²,
H05VV-F
Indoor-to-
Outdoor power
cable
4G X 1.5 mm²,
H07RN-F
4G X 1.5 mm²,
H07RN-F
3G X 1.0 mm²,
H07RN-F
1 X 0.75 mm²,
H05RN-F
Type GL
20 A
25A
25A
Model
✴✴
09/12
✴✴
SS
✴✴
18/24
✴✴
SS/TC
Power cable
(Outdoor unit)
3G X 2.5 mm², H07RN-F
Outdoor-to-
Indoor power
cable
3G X 1.0 mm², H07RN-F
Communication
cable
2 X 0.75 mm², H05RN-F
Type GL
20 A
25 A
N(1) 1
2
✴✴
09/12
✴✴
TC
✴✴
10/13/18/24
✴✴
UN
✴✴
09/12/18/24
✴✴
ME
✴✴
09/12/18/24
✴✴
SS
✴✴
18/24
✴✴
TC
Fasten the screws for the wire holders.