Installing and connecting the drain hose of the outdoor unit

Frame

Ground

Estimated 

snow fall

Snow-proof hood

Bottom surface of outdoor unit

Drain hose

Drain hole

Drain plug

While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate.  For adequate 

draining, do the following:

The outdoor unit is loaded with sufficient R410A refrigerant.  Do not vent R410A into atmosphere: it is a fluorinated 

greenhouse gas,  covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975. 
You should purge the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor.  

It may cause reduction of cooling capacity and malfunction. Refrigerant for air purging is not charged in the outdoor unit. 

Use Vacuum Pump as seen in the picture. 

1.  Insert the drain plug into the drain hole on the underside of the outdoor unit.

1.  Connect each assembly pipe to the appropriate valve on the outdoor unit and 

tighten the flare nut.

2.  Tighten the flare nut first with your hands, and then with a torque wrench, 

applying the following torque:

2.  Connect a drain hose to the drain plug.

3.  Ensure that condensation draining is adequate.

Drain hole

Drain plug

•   To avoid drain plug from contacting the ground, secure gap between the 

ground and the bottom surface of the outdoor unit.

•   In areas with heavy snow fall, piled snow could block the air intake. 

 

To avoid this incident, install a frame that is higher than estimated snow 

fall. In addition, install a snow-proof hood to avoid snow from piling on the 

outdoor unit.

•   When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first 

before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works 

with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle 

abnormally high. It may cause explosion and injury.

Purging the connected pipes

Outdoor unit

Indoor unit

Gas pipe side

Liquid pipe side

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

•  Excessive torque can be cause of gas leakage.

•   Make the electrical connection and leave the system into “stand by 

mode”. Do not turn on the system!

 

This is necessary for better vacuum operation (full OPEN position of 

Electronic Expansion Valve - EEV -).

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

Maldive EUR_AQV09P@_IBIM_33360A_E.indd   34

2011-3-19   11:24:47

Содержание AQV07PSBN

Страница 1: ...Maldive EUR_AQV09P _IBIM_33360A_E indd 1 2011 3 19 11 23 39...

Страница 2: ...es 26 Fixing the installation plate 27 Connecting the assembly cable 28 Installing and connecting the assembly pipe of the indoor unit 30 Purging the indoor unit 31 Cutting or extending the pipe 31 In...

Страница 3: ...ly so that the electric part of the outdoor unit is not exposed Failing to do so may result in electric shock or fire Do not install this appliance near a heater inflammable material Do not install th...

Страница 4: ...a gas leak such as propane gas LP gas etc ventilate immediately without touching the power plug Do not touch the appliance or power cord Do not use a ventilating fan A spark may result in an explosion...

Страница 5: ...hock fire or problems with the product Do not drink the water from the air conditioner The water may be harmful to humans Do not apply a strong impact to the remote controller and do not disassemble t...

Страница 6: ...less Condensation may occur on the indoor unit with risk to have either water blow off or drop on the floor Heating 27 C or less 15 C 24 C Internal protection triggers and the air conditioner will st...

Страница 7: ...r conditioner may slightly look different from illustration shown above depending on your model Checking the name of the parts Air flow blade left and right Air filter under the panel Air flow blade u...

Страница 8: ...uch as Auto Low Medium High Set Set the timer mode Cancel Cancel the timer mode Air swing Activate Deactivate air flow blade movement automatically up and down Mode Set one of the 5 operating modes se...

Страница 9: ...rear side of the remote controller and pull up 2 Insert two AAA batteries Check and match the and signs accordingly Make sure you have inserted the batteries in correct position 3 Close the cover by...

Страница 10: ...ur room Cool In Cool mode the air conditioner will cool your room You can adjust the temperature and the fan speed to feel cooler in hot season If current outside temperatures are much higher than the...

Страница 11: ...ss the button to adjust the temperature Auto You can adjust the desired temperature by 1 C within the range of 16 C 30 C Cool You can adjust the desired temperature by 1 C within the range of 16 C 30...

Страница 12: ...obutton on the remote controller during Cool mode Turbo indicator appears on the remote controller display and the air conditioner operates inTurbo function for 30 minutes Move the blade pin lever lef...

Страница 13: ...sleep if the is set too short or long because the default is set to 8 hour operation If the mode is set less than 4 hours the operation will stop at the same time If the mode is set over 5 hours it w...

Страница 14: ...dicator stops blinking and reserved time will be displayed for 3 seconds If you don t press Set button within 10 seconds after selecting the time the air conditioner will return to previous status Che...

Страница 15: ...ll set the temperature range limit to help you save energy while the air conditioner is operating in Cool mode Press the SmartSaver button on the remote controller while the air conditioner is operati...

Страница 16: ...on the indoor unit display appears and the Auto cleaning function runs Press the AutoClean button once again Cancel Auto Cleaning time can vary depending on the previously used mode Auto cool Cool Dr...

Страница 17: ...acid hydrochloric acid organic solvents such as thinner kerosene and acetone etc to clean the surface of the product or put any stickers on it They may damage the surface of the air conditioner Be car...

Страница 18: ...e Air filter in a ventilated area Clean the Air filter with a vacuum cleaner or soft brush If dust is too heavy rinse it with running water Clean the Air filter every 2 weeks or when the filter clean...

Страница 19: ...1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote controller batteries 1 Outdoor unit Clean the heat exchanger on the outsi...

Страница 20: ...air does not come out If the doors or windows are open it may cause bad cooling heating performance Close the doors and windows Check if the air conditioner has just been turned on after stopping cool...

Страница 21: ...refrigerant flow movement changes It is normal Smoke is generated from the outdoor unit If may not be a fire but it can be a steam generated by the defrost operation from outdoor heat exchanger durin...

Страница 22: ...uld be used only for the applications for which it has been designed the indoor unit is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch...

Страница 23: ...s required by current regulations in force with slings trucks scaffolding or any other means of elevation won t be considered in warranty and charged to end user Power supply line fuse or circuit brea...

Страница 24: ...oid the following places to prevent malfunction of the unit Where there is machine oil Salty environment such as seaside areas Where sulfide gas exists Other special atmosphere areas 125mm or more 300...

Страница 25: ...0 or more The upper part of the outdoor unit and the air outlet is opposite the wall When the walls are blocking front and the rear side of the outdoor unit 300 or more 1500 or more Top view Side view...

Страница 26: ...the air conditioner The number of each accessory is indicated in parentheses Accessories in the indoor unit case Accessories in the outdoor unit case Installation Plate 1 Remote controller 1 Batterie...

Страница 27: ...er Pipe Bender Spirit Level Screw Driver Spanner Drill LWrench MeasuringTape Tools for test operations Thermometer Resistance Meter Electroscope You can select the direction of the drain hose dependin...

Страница 28: ...length It may cause fire Make sure that a wall can withstand the weight of the product If you install the product in a place where it is not strong enough to withstand the product weight the unit cou...

Страница 29: ...unit Ground wire Green Yellow Ground wire Green Yellow Indoor unit Outdoor unit Ground wire Green Yellow Ground wire Green Yellow End of the wire must be circular Also circular terminal must be match...

Страница 30: ...ressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used There are 2 refrigerant pipes of different diameters The smalle...

Страница 31: ...he length of the pipe can be Extended up to see table page 24 Shorten up to see page 24 If you need a pipe longer than 5 meters You must extend the assembly cable You must add refrigerant to the pipes...

Страница 32: ...first with your hands and then with a torque wrench applying the following torque 7 For further details on how to connect to the outdoor unit and purge the air refer to page 34 36 Correct Uneven Thic...

Страница 33: ...and turning to the left 3 Insert the drain hose by fixing it with the screw into the groove of the drain hose and the outlet of the drain pan 4 Attach the rubber cap with a screwdriver by turning it t...

Страница 34: ...e Drain hole Drain plug To avoid drain plug from contacting the ground secure gap between the ground and the bottom surface of the outdoor unit In areas with heavy snow fall piled snow could block the...

Страница 35: ...the service port cap to the valve and tighten them at the torque of 183kgf cm with a torque wrench 8 Check for a gas leak paying particular attention to the 3 way valve s stem nuts and to the service...

Страница 36: ...harge the refrigerant Important information regulation regarding the refrigerant used Charging the refrigerant under conditions of liquid by using a liquid pipe a Factory refrigerant charge of the pro...

Страница 37: ...tem and create vacuum according to page 34 36 After opening valves check leaks using a leak detector for refrigerant Pump down before disconnecting the refrigerant connections for unit repair removal...

Страница 38: ...as indicated on the top of the unit to let the discharged air out properly 2 Fix the outdoor unit in level to an appropriate support using anchor bolts 3 If the outdoor unit is exposed to strong wind...

Страница 39: ...of the air conditioner 6 Disconnect the pipes 3 Press the Airswing button and check the following The airflow blades work properly 4 Press the Power button to stop the operation 2 Press the Mode butto...

Страница 40: ...contraction tube in the middle of the insulation tape 5 Apply heat to the contraction tube to contract it 6 After tube contraction work is completed wrap it with the insulation tape to finish How to c...

Страница 41: ...ide of the Panel frame 4 Find the PCB wire and connect the wire to the Sub PCB as seen in the picture 5 Connect the wire remote controller central remote controller etc to the Sub PCB 6 Assemble the C...

Страница 42: ...amsung com KOSOVO 381 0113216899 LUXEMBURG 261 03 710 www samsung com MACEDONIA 023 207 777 MONTENEGRO 020 405 888 NETHERLANDS 0900 SAMSUNG 0900 7267864 0 10 Min www samsung com NORWAY 815 56 480 www...

Страница 43: ...ser installation manual imagine the possibilities Thank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register DB98 33360A 1...

Отзывы: