3-2-3 Indoor Unit Fan Motor Error
Alignment and Adjustments
3-6
Samsung Electronics
1. Checklist :
1) Is the indoor unit fan motor properly connected with the connector (CN72)?
2) Is the AC voltage correct?
3) Is HALL IC in indoor fan motor properly connected with the connector (CN44)?
4) Is the running capacitor (CR71) properly connected with PCB board?
2. Troubleshooting procedure
After unplugging out the power cord should
be reconnected within 5 seconds.
Does the OPERATION lamp blink?
Does the Solid State Relay(SS71) work properly?
Is the supply voltage of the fan motor sufficient?
Test rod location
PCB CN72
Condition
About AC180V
Normal
voltage
pin #3 and #5
Fan operating
Yes
Yes
Yes
Yes
No
No
No
Check as in the procedure "No power".
PCB is
out of order.
PCB should be replaced.
Replace Motor
Fan-Capacitor
Fan motor should be replaced.
Fan motor is out of order.
Motor Fan-Capacitor is out of order
Test rod location
+
-
SS71-
SS71-
12V
Normal
Voltage
Micom is
out of order.
Micom should be replaced
Error Mode
LAMP
7-segment Display
Indoor Unit Fan Motor Malfunction
Содержание AQ09MSBN
Страница 13: ...MEMO Samsung Electronics 5 4 ...
Страница 35: ...MEMO Samsung Electronics 3 15 ...
Страница 57: ...Samsung Electronics 7 Wiring Diagram This Document can not be used without Samsung s authorization Q H P 7 1 ...
Страница 58: ...Samsung Electronics This Document can not be used without Samsung s authorization Q C O 7 2 ...
Страница 66: ...Operating Instructions and Installation Samsung Electronics 6 4 ...
Страница 70: ...Operating Instructions and Installation Samsung Electronics 6 8 ...
Страница 80: ...Operating Instructions and Installation Samsung Electronics Q MAIN PCB DB93 04418D cont 6 18 ...
Страница 86: ...Operating Instructions and Installation Samsung Electronics JS OMFU 3FBS JS OMFU 3FBS 11 2 ...
Страница 89: ...Samsung Electronics 11 3 Wireless Remote Control Buttons and Display 11 5 ...