I
NSTALLING THE
O
UTDOOR
U
NIT
E-
35
Electrical Work
1 The supply voltage must be the same as the rated voltage of the air conditioner.
2 Prepare the power souce for exclusive use with the air conditioner.
3 Use 15 amperes time delay fuse or circuit breaker.
➢
When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
➢
Otherwise, the shot circuit in the NFB may be occur.
Model
Power supply
Power cable
Assembly cable
Operating current
Starting Current
Power consumption
AS12
✴✴
VC
208-230V~/60Hz Single phase
6A
33A
1280W
AS09
✴✴
VA
115V~/60Hz Single phase
8 A
45A
880W
10
3
AS07
✴✴
VA
115V~/60Hz Single phase
6 A
34A
670W
10
3
Auxiliary Circuit Breaker
N L 1 2 3
N
L
E
Outdoor
unit
Distribution
board
conduit kit
Auxiliary
power
s/w
◆
Auxiliary circuit breaker should be installed near outdoor unit so that each
access is possible.
Main/outdoor power supply cable are connected to upper/lower terminal of
auxiliary circuit breaker.
◆
It is necessary that the conduit kit for power supply to the outdoor unit be
installed between auxiliary power S/W and the outdoor unit.
(the conduit kit is optional)
3G AWG14
4G AWG14 + 1G AWG18