background image

E-

28

INSTALLATION METHOD

660mm (26")

335mm (

13     

)

16 

3 "

Anchor bolt fixing dimensions

Outdoor Unit

❏ 

When using the anchor bolt

1. Fix the unit on a flat, rigid floor using the anchor bolt.

(Anchor bolt : M10 x 4 points - separately purchased)

Installation Procedures

1. Open the front panel, and remove the flare nut.

2. Bend the connection pipe to an appropriate length using the spring bender depending 

upon the installation place.

- Allowable pipe length : Maximum 25m(82ft)
- Allowable pipe drop distance : Maximum 15m(49ft)
- Make no more than ten bending points on the pipe

❈ 

When the pipe length is in excess of the standard pipe length of 5m(16    ft), add the refrigerant 

(R-22) of 40g for each additional 1m(3   ft).

CAUTION

◆ 

If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened.  

Therefore, the pipe length should be as short as possible (less than 15m(49ft)).

Less than 15m(49ft)

Less than 15m(49ft)

Outdoor unit

Indoor unit

Indoor unit

Outdoor unit

 1 

4  

 3 

8  

Содержание APC3240C

Страница 1: ...INSTALACI N MANUEL D UTILISATION MANUEL D INSTALLATION SPLIT TYPE PACKAGED AIR CONDITIONER Cool GRIETA DE COLMADO DE AIRE ACONDICIONADO Refrigeraci n CLIMATISEUR MONOBLOC DE TYPE SPLIT Refroidissemen...

Страница 2: ...to directly contact a designated service center or the outlet at which the product was purchased 7 If the supply cord is damaged it must be replaced by a special cord or assembly available from the m...

Страница 3: ...ng Your Room 10 Removing Excess Humidity 11 Changing the Room Temperature Quickly 12 Selecting the Long Function 13 Airing Your Room 14 Adjusting the Air Flow Direction Vertically 15 Adjusting the Air...

Страница 4: ...Indoor Unit Outer Air Flow Blades Inner Air Flow Blades Control Panel refer to page 5 Air Filter Inside Air Inlet How to open the front panel Hold the upper part of the front panel then pull it sligh...

Страница 5: ...ontrol sensor Fan speed indicators Operating indicators Fan speed selection button On Off button Turbo button Temperature adjustment buttons Power indicator Operating indicators Timer indicator Swing...

Страница 6: ...OL DRY FAN Turbo Sleep Long mode selection button Swing buttons On Timer button Off Timer button On Off Timer Set Cancel button Fan speed adjustment button Temperature adjustment buttons Temperature s...

Страница 7: ...vantage of the unit s features The booklet is organized as follows The following figures are shown on pages from 4 to 6 View of the unit Remote control buttons and display They will help you find the...

Страница 8: ...harged after 12 months even if they have not actually been used You must insert or replace the remote control batteries when You purchase the air conditioner The remote control does not work correctly...

Страница 9: ...necessary press the On Off button Result The POWER indicator on the indoor unit lights up The air conditioner starts up in the mode selected when the unit was last used The indoor unit beeps The air...

Страница 10: ...You can change modes at any time N N N No o o ot t t te e e e To adjust the temperature press the TEMPERATURE buttons one or more times until the required temperature is displayed Possible temperature...

Страница 11: ...It will start up normally after three minutes 2 If the is not displayed at the top of the remote control press the MODE button on the remote control one or more times until it appears Result The indo...

Страница 12: ...lected when the unit was last used The indoor unit beeps 2 Press the button one or more times until is displayed on the remote control Result The temperature and fan settings are adjusted automaticall...

Страница 13: ...il is displayed on the remote control Result The temperature and fan settings are adjusted automatically The air conditioner cools the room as far as possible 3 If you wish to stop the Long function p...

Страница 14: ...15 2 If the is not displayed at the top of the remote control press the MODE button on the remote control one or more times until it appears Result The indoor unit beeps each time you press the MODE...

Страница 15: ...again 2 If you want the blade to move up and down automatically when the air conditioner is operating press the button Result The blades move up and down around the base position set Just as the outer...

Страница 16: ...ton to complete the setting Result The remaining time is displayed Blinking of the timer indicator stops The selected mode and the temperature on the display disappear after 10 seconds The air conditi...

Страница 17: ...nking of the timer indicator stops The air conditioner will switch off automatically when the counter displayed on the remote control reaches the set time and disappears the Off timer setting 2 If you...

Страница 18: ...controlled as indicated in the illustrations below Cooling The desired temperature is increased by 2 F 1 C every hour When it has been increased by 4 F 2 C after two hours the temperature is maintaine...

Страница 19: ...ou should follow when using your air conditioner Power failure If a power failure occurs when the air conditioner is operating the unit is switched off When the power returns the air conditioner start...

Страница 20: ...nction may occur if the heat exchanger freezes High humidity levels Water may condense on and drip from the surface of the indoor unit if it is used for long periods E 20 Mode Outdoor Temperature Indo...

Страница 21: ...ront panel and pull to release them 3 Remove all dust on the air filters with a vacuum cleaner or brush 4 Clean the front panel with a damp cloth and mild detergent do NOT use benzene solvents or othe...

Страница 22: ...oo low or too high Dust may be blocking the air filter guard refer to page 21 for cleaning instructions Check that there is no obstacle in front of the outdoor unit Check that the operating mode is se...

Страница 23: ...al Data Power source Min Ampacity Cooling Watts A W Refrigeration Lines Connections Liquid Line O D Suction Line O D Factory Pre charge Max Line length Max Height Difference mm in mm in m ft m ft m ft...

Страница 24: ...LECTRIC WORK 27 INSTALLATION METHOD Outdoor Unit 28 Installation Procedures 28 Connection of Refrigerant Piping 30 Drilling a Hole in the Wall 31 Drain Hose 31 Connecting the Pipe 31 AIR PURGE 32 REFR...

Страница 25: ...st operation of the unit to check for any problem and then deliver the unit to the customer if the test results are acceptable After completion of test operation hand over the owner s manual installat...

Страница 26: ...with your neighborhood A place where strong wind does not head against the air outlet of the outdoor unit If a strong wind heads directly against the air outlet at the time of cool operation a safety...

Страница 27: ...o Connect the connection wire 1 2 3 and power cable L1 L2 to terminals through the conduit hole as shown in the diagram When the wiring harnesses of the indoor and outdoor unit are not properly connec...

Страница 28: ...ing upon the installation place Allowable pipe length Maximum 25m 82ft Allowable pipe drop distance Maximum 15m 49ft Make no more than ten bending points on the pipe When the pipe length is in excess...

Страница 29: ...sure to insulate the pipe with appropriate insulation material 5 Insert the drain hose into the drain pipe and connect them by tying them to the cable tie to prevent any water leakage 6 After completi...

Страница 30: ...g of the pipe successfully at one time Bending and unbending the pipe more than twice makes the bending work increasingly difficult 3 You may use the spring inserted into the gas pipe instead of the b...

Страница 31: ...the area for piping connection slightly with a hammer a hole is made CAUTION 1 As the draining is of natural drain type make the drain hose direct downward 2 If there is any foreign substance in the...

Страница 32: ...10 minutes Close the valve of the low pressure side of manifold gauge clockwise Make sure that pressure gauge show 0 1MPa 76cmHg after about 10 minutes This procedure is very important in order to avo...

Страница 33: ...n liquid form Start cooling operation Open the tank and refill the refrigerant until arriving at the proper pressure Refill the refrigerant slowly checking the pressure Check the pressure of the press...

Страница 34: ...er completion of installation 1 Check the piping connection area for any gas leakage 2 Is the drain hose properly connected 3 Is the insulation of the piping in good condition 4 Is grounding properly...

Страница 35: ...e service valve is opened before attempting to perform the test operation 2 Never attempt to start test operation by force pressing the electronic contactor as it is very dangerous This is very danger...

Страница 36: ...ELECTRONICS Printed in Korea THIS AIR CONDITIONER IS MANUFACTURED BY ESTE AIRE ACONDICIONADO HA SIDO FABRICADO POR CE CLIMATISEUR EST FABRIQUE PAR...

Отзывы: