Troubleshooting
5-2-2 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is the indoor unit fan motor properly connected with the connector (CN73)?
(2) Is the AC voltage corre c t ?
(3) Is HALL IC in indoor fan motor properly connected with the connector (CN43)?
(4) Is the running capacitor properly connected with the terminal?
2 ) Troubleshooting pro c e d u re
After unplugging out the power cord should
be reconnected within five seconds.
Does the operating lamp(Green) blink?
Does the Solid State Relay(SS71) work
properly?
Is the supply voltage of the fan
motor sufficient?
Test rod location
PCB CN73
Condition
Fan operate
AC 180V
Normal
voltage
YES
YES
YES
NO
NO
NO
Check as in the procedur “NO power parts”
Refer tp page 5-2.
Microcomputer is out of order.
PCB is
out of order.
PCB should
be replaced.
Replace MFC
Fan motor
should be replaced.
Fan motor
is out of order.
MF-C is out of order
YES
-
Test rod location
+
SS71-
SS71-
12V
Normal
Voltage
Содержание AM18A1(B1)E09
Страница 2: ...Samsung Electronics Co Ltd DEC 1998 Printed in Korea Code No DB81 10176A 2...
Страница 4: ...1 2 Samsung Electronics MEMO...
Страница 8: ...2 4 Samsung Electronics MEMO...
Страница 24: ...3 16 Samsung Electronics MEMO...
Страница 38: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit...
Страница 40: ...Samsung Electronics 6 3 6 2 Outdoor Unit 11 10 2 10 3 10 5 10 4 10 1 10...
Страница 44: ...6 7 Samsung Electronics MEMO...
Страница 46: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 Main PCB...
Страница 52: ...Samsung Electronics 10 1 10 Schematic Diagrams 10 1 Indoor Unit BLK L SKY BLUE BROWN BLACK PNA4612M XD 220 1 8W...
Страница 53: ...10 2 Remote Control Samsung Electronics 10 2...