Troubleshooting
4-16
Samsung Electronics
غ
Diagnosis and Adjustment (Error Code)
ـ
Error code related to the Communications / Settings / HW
(cont.)
Error mode
Cause
E-321
Error on EVI (ESC) IN temperature sensor (Short or Open)
E-322
Error on EVI (ESC) OUT temperature sensor (Short or Open)
E-323
Error on suction sensor 2 (Short or Open)
E-346
Error due to operation failure of Fan2
E-347
Motor wire of Fan2 is not connected
E-348
Lock error on Fan2 of outdoor unit
E-353
Error due to overheated motor of outdoor unit's Fan2
E-355
Error due to overheated IPM of Fan2
E-361
Error due to operation failure of inverter compressor 2
E-364
Error due to over-current of inverter compressor 2
E-365
V-limit error of inverter compressor 2
E-366
Error due to over voltage /low voltage of inverter PBA2
E-367
Error due to unconnected wire of compressor 2
E-368
Output current sensor error of inverter PBA2
E-369
DC voltage sensor error of inverter PBA2
E-374
Heat sink temperature sensor error of inverter PBA2
E-378
Error due to overcurrent of Fan2
E-385
Error due to input current of inverter 2
E-386
Over-voltage/low-voltage error of Fan2
E-387
Hall IC connection error of Fan2
E-389
V-limit error on Fan2 of compressor
E-393
Output current sensor error of Fan2
E-396
DC voltage sensor error of Fan2
E-399
Heat sink temperature sensor error of Fan2
E-400
Error due to overheat caused by contact failure on IPM of Inverter PBA2
E-407
Compressor operation stop due to high pressure protection control
E-410
Compressor operation stop due to low pressure protection control or refrigerant leakage
E-416
Compressor operation stop due to discharge temperature protection control
E-425
Phase reversal or phase failure (3Ø outdoor unit wiring, R-S-T-N ), connection error on 3 phase input
E-428
Compressor operation stop due abnormal compression ratio
E-438
EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector insertion of EVI (ESC) EEV
E-439
Error due to refrigerant leakage
E-440
Heating mode restriction due to high air temperature
E-441
Cooling mode restriction due to low air temperature
E-442
Refrigerant charing restriction in heating mode when air temperature is over 15 °C
E-443
Operation prohibited due to low pressure
E-445
CCH is deatched
E-446
Error due to operation failure of Fan1
E-447
Motor wire of Fan1 is not connected
E-448
Lock error on Fan1
E-452
Error due to ZPC detection circuit problem or power failure
E-453
Error due to overheated motor of outdoor unit's Fan1
E-455
Error due to overheated IPM of Fan1
Содержание AM072FXVAFH series
Страница 214: ...Samsung Electronics 5 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN...
Страница 219: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Страница 221: ...PCB Diagram and Parts List 5 8 Samsung Electronics ASS YPCBMAIN HUB cont DC 1 1 2 3 4 5 6 7 8 9 10 11...
Страница 223: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Страница 225: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Страница 229: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Страница 231: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Страница 244: ...Wiring Diagram 6 15 Samsung Electronics Wiring Diagram Samsung Electronics 6 16 6 8 AM216KXVGJ6...
Страница 260: ...Samsung Electronics 7 15 7 19 AM038KXWD66 7 20 AM048 055KXWD66...
Страница 274: ...Samsung Electronics 8 13 8 3 How to check the view mode using a tact switch AM6666XV666 rX rY rZ r A type B type...