Check Operation & Amount of Refriherant Automatically Checking
6) 4Way Valve
Ŷ
Inspection item : 4Way Valve of Outdoor Unit.
Ŷ
Error code: None (The resulting report "Undetermined")
Ŷ
Determine the 4Way Valve operation status of the each Outdoor Unit.
Ŷ
If the judgment of 4Way Valve is "Undetermined" : Checking in accordance with the following order.
Yes
No
Yes
No
Yes
No
Yes
No
Commissioning results,
is Valve and Pressure sensor normal?
Is 4Way Valve connector properly connect?
Is 4Way Valve coil normal?
(Wire breaking, operation impossible, etc.)
Is PCB Output signal normal?
Replace 4Way Valve Body
(Retry the Automatic Commissioning :
If the continuous "Undetermined" is displayed.
Complete
Check the corresponding Pressure sensor.
Confirmation and Measures
Replace Valve coil
Replace PCB