Samsung Electronics
134
Troubleshooting
4-3-45 DC Link voltage sensor error
Outdoor unit display
(INVERTER1 PBA)
(INVERTER2 PBA)
(OUTDOOR FAN 1 PBA)
Judgment Method
∙ DC voltage detection : Error judgment where the voltage value is more than 4.8V or less than 0.2V.
Cause of problem
∙ DC Link Connector disconnected
∙ PBA voltage sensing circuit defective
Check the connector
connection
Check the status of DC LINK Connector
Power Off
Replace FAN PBA
E496
E469
Replace No1 INVERTER PBA
E369
Replace No2 INVERTER PBA
1. Cause of problem
DC power wire (Inv. PBA)
DC power wire (Fan PBA)
4-3 Appropriate Measures for Different Symptom
(cont.)
Содержание AM038KXWDCH
Страница 147: ...Samsung Electronics 144 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont ...
Страница 149: ...Samsung Electronics 146 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont ...
Страница 168: ...Samsung Electronics 165 5 PBA Diagram and Parts List 5 1 ASS Y PBA MAIN Ŷ Push buttons Type ...
Страница 170: ...PBA Diagram and Parts List Samsung Electronics 167 5 1 ASS Y PBA MAIN cont Ŷ DIP S W Type ...
Страница 172: ...PBA Diagram and Parts List Samsung Electronics 169 5 2 ASS Y PBA MAIN HUB Ŷ AC ...
Страница 174: ...PBA Diagram and Parts List Samsung Electronics 171 5 2 ASS Y PBA MAIN HUB cont Ŷ DC ...
Страница 178: ...PBA Diagram and Parts List Samsung Electronics 175 5 3 ASSY PBA INVERTER cont Model AM300KXWANR AM240KXWAF J R ...
Страница 181: ...PBA Diagram and Parts List Samsung Electronics 178 5 4 ASS Y PBA EMI cont Model AM300KXWANR AM240KXWAF J R ...