KEY OPTION
56
Tact S/W
# of Times
Item
SEG1
SEG2
SEG3
SEG4
Note
K1
Auto Commissioning & Management System
One time of
long press
K1
1time
Charge heating refrigerant
2times
Test heating operation
3times
Heating pump out
4times
Vacuum
5times
Finish
K2
1time
Charge cooling refrigerant
2times
Test cooling operation
3times
Cooling pump down
4times
Test operation for checking refrigerant level
5times
Finish
K3
Reset
Tact S/W
# of Times
Item
SEG1
SEG2
SEG3
SEG4
Note
K1
1time
Charge heating refrigerant
2times
Test operation of heating
3times
Heating pump out
4times
Vacuum
5times
Finish
K2
1time
Charge cooling refrigerant
2times
Test operation of cooling
3times
Cooling pump down
4times
Finish
K3
Reset
■
AM
SSSSS
M
SSS
series
■
RD
SSS
M
SSSS
series
■
K4 Display Order
K4
Display Details
Display Value (Ex.)
Meaning
SEG1
SEG 2,3,4
1time
Operating frequency of current compressor
1
0,4,2
42Hz
2times
Low pressure value (AM
SSSSS
M
SSS
series)
2
1,7,5
1.75Mpa
Target frequency (RD
SSS
M
SSSS
series)
0,6,4
64Hz
3times
Outdoor temperature
3
1,5,8
15.8
℃
4times
Discharge temperature of compressor
4
7,7,2
77.2
℃
5times
OLP temperature
5
5,5,8
55.8
℃
6times
COND temperature
6
3,1,7
31.7
℃
7times
Double-pipe heat exchanger temperature
7
1,8,9
18.9
℃
8times
High pressure value
8
2,1,0
2.10MPa
9times
Outdoor fan RPM
9
6,0,0
600 RPM
10times
ESC (EVI) EEV Operating Value
A
0,8,0
80 STEP
11times
MAIN EEV Operating Value
B
1,0,0
1000 STEP
12times
Current Value
C
1,0,0
10A
13times
Number of Indoor Unit Connections
D
0,0,7
7
℃
14times
Number of Indoor Units Operating
E
0,0,4
4
℃
15times
Total Capacity of Connected Indoor Units
F
1,4,5
14.5kcal/hr