Troubleshooting
284
Samsung Electronics
- Setting an indoor unit address and installation option
■
Setting an indoor unit installation option (suitable for the condition of each installation location
)
1. Check whether power is supplied or not.
-
When the indoor unit is not plugged in, there should be additional power supply
in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is 020010-100000-200000-300000.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is more
than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
RESERVED
Exterior temperature
sensor
Central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Drain pump
Hot water heater
Electronic heater
Opening the
electronic expansion
valve
Master / Slave
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control
output
S-Plasma ion
Buzzer
Number of hours
using filter
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control of a
remote controller
Heating setting
compensation
EEV opening of an
indoor unit stopped
during oil return or
Defrost operation.
-
Human sensor
▶
1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
▶
1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to '1000hour' even if the SEG18 is set to
exept for 2 or 6.
▶
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as indoor 1.
▶
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central control
option as 0 (Disuse) to exclude the indoor unit from the central control.
Indoor Unit
1(L)
F2
F1
2(N)
Содержание AM017HN1DEH/EU
Страница 427: ...PCB Diagram and Parts List 430 Samsung Electronics 5 1 4 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 441: ...PCB Diagram and Parts List 444 Samsung Electronics 5 1 11 Duct type HSP BLDC PCB AM112 128 140FNHDEH6 1 2 3 4...
Страница 485: ...PCB Diagram and Parts List 488 Samsung Electronics OAP DUCT AM220 280 NEPEH EU Cont BLDC Driver PCB cont 6 5 4 3 2 1...
Страница 494: ...PCB Diagram and Parts List Samsung Electronics 497 1 2 3 4 5 6 7 10 9 8 STAND Cont Main PCB AM140JNPDKH TK...
Страница 531: ...Wiring Diagram 534 Samsung Electronics AM666MNFDEH6 This Document can not be used without Samsung s authorization...
Страница 539: ...542 Samsung Electronics 6 1 26 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 540: ...Samsung Electronics 543 6 1 27 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 541: ...544 Samsung Electronics 6 1 28 OAP DUCT AM220 280 NEPEH EU This Document can not be used without Samsung s authorization...
Страница 542: ...Samsung Electronics 545 6 1 29 V AHU AM666JNZDCH6 This Document can not be used without Samsung s authorization...
Страница 543: ...546 Samsung Electronics 6 1 30 Stand AM280JNPDKH TK This Document can not be used without Samsung s authorization...
Страница 544: ...Samsung Electronics 547 This Document can not be used without Samsung s authorization AM140JNPDKH TK...