Samsung AM017FNLDEH/EU Скачать руководство пользователя страница 5

04_ safety information

safety information

Make sure that children take precautions against access to the air 

conditioner and they do not play with the unit.

Do not clean the interior of air conditioner on your own.

• You may damage the parts which can cause electric shock or fire

• Consult contact center for cleaning the interior of the air conditioner.

Do not Connect the air conditioner with heating apparatus or attempt to 

disassemble,remodel or repair it yourself.

• Potential risk of malfunction, electric shock or fire. If repairs are needed, 

consult the contact center.

Consult the place of purchase or contact to install,reinstall or 

disassemble the aire conditioner.

• Improper installation carries a risk of unit malfunction, water leakage, electric 

shock or fire.

• If installing in specialty areas, such as a factory complex or saline coastal 

area, consult the place of purchase or contact center for specific installation 

details.

• The units must be installed according to distances declared, in order to 

permit accessibility from each side, either to guarantee correct operation of 

maintenance or repairing products. The unit’s parts must be reachable and 

removable completely under safety condition (for people or things).

Consult a dealer regarding the appropriate measures to prevent the 

allowable concentration from being exceeded.

• If the refrigerant leaks, and cause the concentration limit to be exceeded, 

hazards due to lack of oxygen in the room may result.

If the indoor unit gets wet, turn the power off immediately and call your 

nearest contact center.

• Potential risk of fire or electric shock.

Always make sure that the power supply is compliant with current safety 

standards. Always install the air conditioner in compliance with current 

local safety standards.
Verify that the voltage and frequency of the power supply comply with 

the specifications and that the installed power is sufficient to ensure 

the operation of any other domestic appliance connected to the same 

electric lines.

Use a rated circuit breaker only.

• Never use steel wires or copper wires as a circuit breaker. It may cause fire 

or unit malfunctions.

Do not put undue stress or place heavy object on the power cable.
Do not bend the power cable excessively.

• Potential risk of fire or electric shock.

To protect the product from water and possible shock, you should keep 

the power cable and the connection cord of the indoor and outdoor units 

in the protection tube.
When opening or closing the front panel, use a stable stool and watch 

your steps carefully.

Содержание AM017FNLDEH/EU

Страница 1: ...Air Conditioner user manual imagine the possibilities Thank you for purchasing this Samsung product Duct Type Series Slim duct AM NLD AM022 028 036 NMD Ma duct AM NMD HSP duct AM NHD Home duct AM MNLD ...

Страница 2: ......

Страница 3: ...lp and information online at www samsung com Important safety symbols and precautions WARNING Hazards or unsafe practices that may result in severe personal injury or death CAUTION Hazards or unsafe practices that may result in minor personal injury or property damage CAUTION To reduce the risk of fire explosion electric shock or personal injury when using your air conditioner follow these basic s...

Страница 4: ...aged or dusted power plug power cable or loosened power receptacle Potential risk of fire or electric shock Install an exclusive circuit breaker and short circuit breaker for the air conditioner Potential risk of electric shock or fire Do not insert anything such as fingers or branches into the air conditioner vents while the air conditioner is running Keep the children away from the air condition...

Страница 5: ... completely under safety condition for people or things Consult a dealer regarding the appropriate measures to prevent the allowable concentration from being exceeded If the refrigerant leaks and cause the concentration limit to be exceeded hazards due to lack of oxygen in the room may result If the indoor unit gets wet turn the power off immediately and call your nearest contact center Potential ...

Страница 6: ...llation manual there will be an extra labor charge for installing and construction Potential risk of malfunction electric shock or fire if repairs or installations are attempted by a non qualified service technician Do not spray flammable gases such as insecticide near the air conditioner Potential risk of electric shock fire or unit malfunction Do not open the front grille during operation Potent...

Страница 7: ...ge on delivery If damaged do not install the air conditioner and call the place of purchase immediately Keep indoor temperatures stable and not extremely cold especially where there are children elderly or disabled people The packaging material and used batteries of the remote controller optional must be disposed of in accordance with the national standards The refrigerant used in the air conditio...

Страница 8: ... of complete safety either for people or things For this reason where it is not observed as indicated into the Installation Manual the cost necessary to reach and repair the unit in safety as required by current regulations in force with slings trucks scaffolding or any other means of elevation won t be considered in warranty and charged to end user For use in Europe This appliance can be used by ...

Страница 9: ...ble should not be disposed of with other household waste at the end of their working life To prevent possible harm to the environment or human health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to pro mote the sustainable reuse of material resources Household users should contact either the retailer where they purchased this p...

Страница 10: ...ptimal efficiency Please read the user manual to get started and to make the best use of the air conditioner SLIM DUCT TYPE MA DUCT TYPE Your air conditioner may look slightly different from the illustration shown above depending on your model Air intake Air outlet Ceiling Air filter the return air side Air intake Air outlet Ceiling Air filter the return air side HSP DUCT TYPE Air intake Air outle...

Страница 11: ...is happens The air conditioner stops heating The air conditioner will operate automatically in De ice mode for 10 minutes The steam produced on the outdoor unit in De ice mode is safe No intervention is required after about 10 minutes the air conditioner operates again normally The unit will not operate when it starts to de ice Fan Fan may not operate for about 3 5 minutes at the beginning to prev...

Страница 12: ...de out the Air filter on the rear side panel to the right side 2 Clean the Air filter with a vacuum cleaner or soft brush If dust is too heavy then rinse it with running water and dry it in a ventilated area For best conditions repeat every two weeks If the Air filter dries in a confined or humid area odors may generate If it occurs re clean and dry it in a ventilated area 3 Insert the Air filter ...

Страница 13: ... dry it in a ventilated area For best conditions repeat every two weeks If the Air filter dries in a confined or humid area odors may generate If it occurs re clean and dry it in a ventilated area 3 Insert the Air filter back in its original position The illustration shown above may differ from your depending on your model After cleaning the filter press the Filter Reset button on the remote contr...

Страница 14: ...the air filter 1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote control batteries 1 Outdoor unit Clean the heat exchanger on the outside of the unit 2 Clean the heat exchanger on the inside of the unit 2 Clean the electric components with jets of air 2 Verify that all the electric components are firmly tightened 2 Clean t...

Страница 15: ...o against cold air when the heat pump is heating Anti protection of internal battery The compressor will be off to protect internal battery when the air conditioner operates in Cool mode Protect compressor The air conditioner does not start operating immediately to protect the compressor of the outdoor unit after it has been started If the heat pump is operating in Heat mode De ice cycle is actuat...

Страница 16: ...ilable for cooling model The fan speed does not change Check if you selected Auto or Dry mode The air conditioner automatically adjusts the fan speed to Auto in Auto Dry mode Timer function does not set Check if you press the Power button on the remote control after you have set the time Odors permeate in the room during operation Check if the appliance is running in a smoky area or if there is a ...

Страница 17: ...0 19 AM090FNMDEH EU 1150 480 260 32 AM036FNLDEH EU 700 199 600 19 5 AM112FNMDEH EU 1150 320 480 36 5 AM045FNLDEH EU 900 199 600 24 5 AM128FNMDEH EU 1200 360 650 48 5 AM056FNLDEH EU 900 199 600 24 5 AM140FNMDEH EU 1200 360 650 48 5 AM071FNLDEH EU 1100 199 600 30 AM112FNHDEH EU 1200 360 650 57 AM090FNLDEH EU 1300 295 690 40 AM128FNHDEH EU 1200 360 650 57 AM112FNLDEH EU 1300 295 690 40 AM140FNHDEH EU...

Страница 18: ...on to the unit before placing the unit inside the ceiling Note Concrete Suspension bolt Φ9 52 or M10 Hole in anchor Hole in plug Insert Ceiling support 6 Screw the nuts to suspend the unit 7 Adjust level of the unit by using measurement plate for all 4 sides For proper drainage of condensate give a 10mm 3mm slant to the left or right side of the unit which will be connected with the drain hose as ...

Страница 19: ...g Cooling Remarks Standard 30 C 85 High humidity 30 C over85 EPDM NBR Liqued Φ6 35 Φ9 52 9t 9t Internal temperature is higher than 120 C pipe Φ12 7 Φ50 80 13t 13t Gas Pipe Φ6 35 13t 19t Φ9 52 19t 25t Φ12 70 Φ15 88 Φ19 05 Φ22 23 Φ25 40 Φ28 58 32t Φ31 75 Φ38 10 Φ44 45 Φ50 80 25t 38t 1 Install the drain hose as short as possible In order to discharge condensation water the drain hose should keep tilt...

Страница 20: ...to each installation manual about the rating current of indoor unit Decide the power cable specification and maximum length within 10 power drop among indoor units T Coef 1 55 T Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Without the drain pump 1 1 5m Horizontal drainpipe more than 1 100...

Страница 21: ... button and LowTemp button 3 Check if you have entered the option setting status Step 2 The procedure of option setting After entering the option setting status select the option as listed below The procedure of option setting SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 0 X X X X X 1 X X X X X SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 ...

Страница 22: ...ime you press the button will be selected in rotation 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SE...

Страница 23: ...G17 value Each time you press the button will be selected in rotation 14 Setting Dry mode Press Mode button to be change to Dry mode in the OFF status 15 Setting SEG18 SEG20 option Press Low Fan button to enter SEG18 value Press High Fan button to enter SEG20 value Each time you press the button will be selected in rotation 16 Setting Fan mode Press Mode button to be change to Fan mode in the OFF ...

Страница 24: ...etails Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE __ SettingRMCaddress __ Groupchannel 16 Groupaddress Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indicatio...

Страница 25: ...t External heater On or Off signal S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation Removing condensated water in heating mode EEV Step of stopped unit during oil return defrost mode Motion detect sensor 1WAY 2WAY 4WAY MODEL Drain pump SEG8 will be set to USE 3minute delay even if the drain...

Страница 26: ...0 Disuse 1 Use Disuse 1 RPM compensation 1 Use 2 Disuse Use 1 1 Use 2 Highceiling KIT 3 Use Use 1 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Useofdrainpump Useofhotwater heater EEVStepwhenheating stops Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 Disuse 0 Disuse 0 ...

Страница 27: ...anation PAGE Individualcontrolof aremotecontroller Heatingsettingcompensation Removing condensatedwaterinheatingmode EEVStepofstopped unitduringoilreturn defrostmode Motiondetectsensor Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details HeatingSetting Compensation Removing Condensated Waterin Heating Mode 3 ...

Страница 28: ...efollowing2or3isusedasexternalheaterOn Offsignal thesignalformonitoringexternalcontactcontrolwillnotbeoutput 2 Fanisturnedoncontinuallywhentheexternalheateristurnedon 3 Fanisturnedoffwhentheexternalheateristurnedonwithcoolingonlyindoorunit Coolingonlyindoorunit Tousethisoption installtheModeSelectswitch MCM C200 ontheoutdoorunitandfixitascoolmode IfFanissettooffforcoolingonlyindoorunitbysettingthe...

Страница 29: ... C 2 2 C 3 1 5 C 3 1 5 C 3 2 5 C 4 2 C 4 2 C 4 3 C 5 2 5 C 5 2 5 C 5 3 5 C 6 3 C 6 3 C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE WhensettingSEG3 Standardformode changingCooling Heatingmode WhensettingSEG3 Timerequiredfor modechange Compensationoption forLongpipeorheight diffferencebetween indoorunits Remote Controller Display Indication andDetails Indic...

Страница 30: ...heateristurnedonatthesametimeastheheatingthermostatis on andturnedoffwhentheheatingthermostatisoff e g 2 Setting02seriesSEG15 2 Setting05seriesSEG18 A Roomtemp settemp f heatingcompensationtemp Externalheateristurnedonwhenthetemperatureismaintainedas4 5 Cfor10minutes Roomtemp settemp f heatingcompensationtemp Externalheateristurnedoffwhenthetemperatureismaintainedas4 5 C 1 C 1 CistheHysteresisforO...

Страница 31: ...hange Theunitdigitofan optionSEGyouwill change Thechangedvalue Indication 0 D 2 1 7 1 When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Note SEG 3 4 5 6 8 9 additional information WhentheSEG3issetas 1 andfollowAutoChangeOverforHRonlyoperati...

Страница 32: ...00 800 500 55 500 GSM 7799 www samsung com uz_ru support KYRGYZSTAN 00 800 500 55 500 GSM 9977 www samsung com support TAJIKISTAN 8 10 800 500 55 500 GSM 8888 www samsung com support MONGOLIA 1800 25 55 www samsung com support BELARUS 810 800 500 55 500 www samsung com support UKRAINE 0 800 502 000 www samsung com ua support COUNTRY CALL ORVISITUSONLINEAT MOLDOVA 373 22 667 400 www samsung com sup...

Отзывы: