Installing the unit

IMPORTANT:  When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines.  

Always disassemble the electric lines before the refrigerant tubes.

f

f

Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged, DO NOT 

INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the 

material from the retailer.)

f

f

After completing the installation, always carry out a functional test and provide the instructions on how to operate the air conditioner 

to the user.

f

f

Do not use the air conditioner in environments with hazardous substances or close to equipment that release free flames to avoid the 

occurrence of fires, explosions or injuries.

f

f

Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both sides 

and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible and easy to disassemble 

without endangering people and objects.
For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair the 
units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaffolding or any other elevation 
system will NOT be considered part of the warranty and will be charged to the end customer.

Power supply line, fuse or circuit breaker

f

f

Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance 

with current local safety standards.

f

f

Always verify that a suitable grounding connection is available.

f

f

Verify that the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient to 

ensure the operation of any other domestic appliance connected to the same electric lines.

f

f

Always verify that the cut-off and protection switches are suitably dimensioned.

f

f

Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram 

included in the manual.

f

f

Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric specifications and 

with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable to the 

installation of air conditioners.

f

f

Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category.

•  Make sure that you earth the cables.

 - Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is not complete, 

electric shock or fire may occur.

•  Install the circuit breaker.

 - If the circuit breaker is not installed, electric shock or fire may occur.

•  Make sure that the condensed water dripping from the drain hose runs out properly and safely.
•  Install the power cable and communication cable of the indoor and outdoor unit at least 1m away from the electric 

appliance.

•  Install the indoor unit away from lighting apparatus using the ballast.

 - If you use the wireless remote controller, reception error may occur due to the ballast of the lighting apparatus.

•  Do not install the air conditioner in following places.

 - Place where there is mineral oil or arsenic acid. Resin parts flame and the accessories may drop or water may leak. 

The capacity of the heat exchanger may reduce or the air conditioner may be out of order.

 - The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.

•  The copper pipe or connection pipe may corrode and refrigerant may leak.

 - The place where there is a machine that generates electromagnetic waves. The air conditioner may not operate 

normally due to control system.

 - The place where there is a danger of existing combustible gas, carbon fiber or flammable dust.

•  The place where thinner or gasoline is handled. Gas may leak and it may cause fire.

CAUTION

Safety precautions

Содержание AM Series

Страница 1: ......

Страница 2: ... f Inordertopreventelectricshocks firesorinjuries alwaysstoptheunit disabletheprotectionswitchandcontactSAMSUNG stechnical supportiftheunitproducessmoke ifthepowercableishotordamagedoriftheunitisverynoisy f f Alwaysremembertoinspecttheunit electricconnections refrigeranttubesandprotectionsregularly Theseoperationsshouldbe performedbyqualifiedpersonnelonly f f Theunitcontainsmovingparts whichshould...

Страница 3: ...yotherdomesticapplianceconnectedtothesameelectriclines f f Alwaysverifythatthecut offandprotectionswitchesaresuitablydimensioned f f Verifythattheairconditionerisconnectedtothepowersupplyinaccordancewiththeinstructionsprovidedinthewiringdiagram includedinthemanual f f Alwaysverifythatelectricconnections cableentry sectionofleads protections arecompliantwiththeelectricspecificationsand withtheinstr...

Страница 4: ...becooled f f Pre planforeasyandshortroutingoftherefrigeranttubingandwiringtotheoutdoorunit f f Thereshouldbenoflammablegas alkaline substancespresentintheair f f Avoidlocationwhereobstaclespreventinggoodaircirculationarepresent f f Noisepreventionshouldbeconsideredindeterminingtheunit slocation f f Thestructure wheretheunitistobeinstalledshouldbestrongenoughtosupporttheweightoftheunit f f Rigidwal...

Страница 5: ...9 52 3 8 2 Gaspipeconnection ø15 88 5 8 3 Drainpipeconnection ODø25 IDø20 Model Dimension A B AM112JNCDKH 1350 1298 AM140JNCDKH 1650 1598 Dimensionoftheindoorunit 235 260 66 156 260 675 A B 01 03 02 Pipeoutlet Wiringhole Drainhoseoutlet Airintakehole Ø100 ...

Страница 6: ...ding on the ceiling type Ensurethattheceilingisstrongenoughtosupporttheweight oftheindoorunit Beforehangingtheunit testthestrengthof eachattachedsuspensionbolt Ifthelengthofsuspensionboltismorethan1 5m itisrequired topreventvibration Ifthisisnotpossible createanopeningonthefalseceilingin ordertobeabletouseittoperformtherequiredoperationson theindoorunit CAUTION 5 Screw eight nuts to the suspension...

Страница 7: ...Hang the indoor unit to the suspension bolts between two nuts Pipingmustbelaidandconnectedinsidetheceilingwhen suspendingtheunit Iftheceilingisalreadyconstructed laythe pipingintopositionforconnectiontotheunitbefore placingtheunitinsidetheceiling CAUTION 9 Screw the nuts to suspend the unit 10 Adjust level of the unit by using measurement plate for all 4 sides Forproperdrainageofcondensate givea1 ...

Страница 8: ...uallyandthenwithatorque wrench aspannerapplyingthefollowingtorque Outer Diameter Torque kgf cm N m ø 6 35 mm 140 180 14 18 ø 9 52 mm 350 430 34 42 ø 12 70 mm 500 620 49 61 ø 15 88 mm 690 830 68 82 Mustapplyrefrigerantoilontheflaringareatopreventaleak NOTE 3 Besurethattheremustbenocrackorkinkonthebendedarea Ifbracketatrightsidebedisturbedwhenconnectingthepipe the installercandetachitbyremoving2scre...

Страница 9: ...ng Uneven Thickness Cracked DamagedSurface Inclined Correct 6 Alignthepipesandtightentheflarenutsfirstmanuallyandthenwithatorquewrench applyingthefollowingtorque Outer diameter mm ConnectionTorque Flare dimension mm Flare shape mm kgf cm N m ø6 35 140 180 14 18 8 70 9 10 R 0 4 0 8 90 2 45 2 ø9 52 350 430 34 42 12 80 13 20 ø12 70 500 620 49 61 16 20 16 60 ø15 88 690 830 68 82 19 30 19 70 Ifthepipes...

Страница 10: ...ttherearenoleaksinthesystem you caninsulatethepipingandhose 1 Toavoidcondensationproblems placeAcrylonitrileButadienRubber separatelyaroundeachrefrigerantpipe 2 Windinsulatingtapearoundthepipesanddrainhoseavoidingto compresstheinsulationtoomuch 3 Finishwrappinginsulatingtapearoundtherestofthepipesleadingto theoutdoorunit 4 Thepipesandelectricalcablesconnectingtheindoorunitwiththe outdoorunitmustbe...

Страница 11: ...itionsbelow usethesameinsulationthatisusedforhighhumidity conditions Geologicalcondition Highhumidityplacessuchasshoreline hotspring nearlakeorriver andridge whenthepartofthebuildingis coveredbyearthandsand Operationpurposecondition Restaurantceiling sauna swimmingpooletc Buildingconstructioncondition Theceilingfrequentlyexposedtomoistureandcoolingisnotcovered e g Thepipeinstalledatacorridorofador...

Страница 12: ...oseaccordingtothefigure f f Windandwrapflexiblehoseclampanddrainhosefullywiththermalinsulationsponge fixbothendsofexternallayer withribbonforthermalinsulation f f Afterbeinginstalled drainhosemustbeinsulatedfullybyheatinsulatingmaterial Tobeprovidedatsite A A Flexiblehoseclamp ofdrainhose Jointofdrainhose Drainhose Drainhose FixwithCable Tie Wrapthermalsleevehose Indoor unit Asshowninthefigure tig...

Страница 13: ... 7 0 2 4 1 6 16 4 3 0 2 0 0 7 4 8 2 5 4 6 6 0 2 4 2 0 3 0 2 2 3 0 2 6 6 17 5 4 3 0 2 0 0 8 4 8 5 4 4 9 5 0 2 5 6 0 3 0 2 3 4 0 2 6 5 20 4 3 0 2 0 0 9 Powerandcommunicationcableconnection 1 Before wiring work you must turn off all power source 2 Indoor unit power should be supplied through the breaker ELCB or MCCB ELB separated by the outdoor power ELCB Earth Leakage Circuit Breaker MCCB Molded Cas...

Страница 14: ...ecide the capacity of ELCB or MCCB ELB by below formula Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloro prene sheathed flexible cord Code designation IEC 60245 IEC 57 CENELEC H05RN F or IEC 60245 IEC 66 CENELEC H07RN F The capacity of ELCB or MCCB ELB X A 1 25 X 1 1 X Ai T X The capacity of ELCB or MCCB ELB T Ai Sum of Rating currents of each indoor u...

Страница 15: ...ercabletotheauxiliarycircuitbreaker Anallpoledisconnectionfromthepowersupplymustbeincorporatedinthefixedwiring 3mm Youmustkeepthecableinaprotectiontube Keepdistancesof50mmormorebetweenpowercableandcommunicationcable Maximumlengthofpowercablesaredecidedwithin10 ofpowerdrop Ifitexceeds youmustconsideranotherpower supplying method Thecircuitbreaker ELCBorMCCB ELB shouldbeconsideredmorecapacityifmanyi...

Страница 16: ...heindoorunit Seethe picture 2 AttachtheInterfacemodulePCBtothecaseinthecontrolboxoftheindoorunit then connectthepowerandthecommunicationcablebetweentheInterfacemoduleand theindoorunit 3 IfyouinstallaInterfacemoduletoanindoorunit everyoutdoorunitwhichisconnected toanindoorunitcanbecontrolledsimultaneously 4 EachindoorunitconnectedtothesamecentralizedcontrollerhasitsownInterface module ...

Страница 17: ...G5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 0 X X X X X 1 X X X X X SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X On SEG1 12 Off SEG13 24 Theprocedureofoptionsetting Option setting is available from SEG1 to SEG 24 SEG1 SEG7 SEG13 SEG19 are not set as page option Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18 SEG20 24 as OFF status Settinganind...

Страница 18: ... will be selected in rotation SEG6 SEG8 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation SEG9 SEG10 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG11...

Страница 19: ...n to enter SEG21 value Press High Fan button to enter SEG22 value Each time you press the button will be selected in rotation SEG21 SEG22 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG23 ...

Страница 20: ...ls Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE __ SettingRMCaddress __ Groupchannel 16 Groupaddress Indication andDetails Indication Details Indication Details Indication Details Indication Details 1 0 NoRMC address RMC1 0 F RMC2 0 F 1 RMC address setting ...

Страница 21: ...nal control output External heater On or Off signal S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation Removing condensated water in heating mode EEV Step of stopped unit during oil return defrost mode Motion detect sensor 1WAY 2WAY 4WAY MODEL Drain pump SEG8 will be set to USE 3minute delay ...

Страница 22: ...Details Useof External room temperature sensor Minimizingfan operationwhen thermostatisoff 0 2 0 Disuse 0 Disuse Disuse 0 Disuse 0 Disuse 1 Use Disuse 1 RPM compensation 1 Use 2 Disuse Use 1 1 Use 2 Highceiling KIT 3 Use Use 1 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Useofdrainpump Useofhotwater heater EEVStepwhenheating stops Indication andDetails Indication Details Indication Det...

Страница 23: ...troller Heatingsettingcompensation Removing condensatedwaterinheatingmode EEVStepofstopped unitduringoilreturn defrostmode Motiondetectsensor Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details HeatingSetting Compensation Removing Condensated Waterin Heating Mode 3 0or1 channel1 0 Default 4 Disuse 0 Default value 0 Disuse 1 Turnoutin...

Страница 24: ...terOn Offsignal thesignalformonitoringexternalcontactcontrolwillnotbeoutput 2 Fanisturnedoncontinuallywhentheexternalheateristurnedon 3 Fanisturnedoffwhentheexternalheateristurnedonwithcoolingonlyindoorunit Coolingonlyindoorunit Tousethisoption installtheModeSelectswitch MCM C200 ontheoutdoorunitandfixitascoolmode IfFanissettooffforcoolingonlyindoorunitbysettingtheSEG9 3orSEG15 3 youneedtouseanext...

Страница 25: ...C 4 3 C 5 2 5 C 5 2 5 C 5 3 5 C 6 3 C 6 3 C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE WhensettingSEG3 Standardformode changingCooling Heatingmode WhensettingSEG3 Timerequiredfor modechange Compensationoption forLongpipeorheight diffferencebetween indoorunits Indication andDetails Indication Details Indication Details Indication Details Indication Detail...

Страница 26: ...theheatingthermostat ison andturnedoffwhentheheatingthermostatisoff e g 2 Setting02seriesSEG15 2 Setting05seriesSEG18 A Roomtemp settemp f heatingcompensationtemp Externalheateristurnedonwhenthetemperatureismaintainedas4 5 Cfor10minutes Roomtemp settemp f heatingcompensationtemp Externalheateristurnedoffwhenthetemperatureismaintainedas4 5 C 1 C 1 CistheHysteresisforOn Offselection Option SEG13 SEG...

Страница 27: ...odecanbechangedwhenThermoOffstatusismaintainedduringthetimewithSEG9 A SetwithSEG4 B SetwithSEG5 C SetwithSEG6 D SetwithSEG8 Cooling Thermo Off Heating Thermo Off Cooling Thermo On Heating Thermo On B C D Ts A c a Temp d b Standardtemp forHeating Standardtemp forCooling Standardtemp for Heating Cooling Standardtemp forCooling Heating Settemp forAutomode ...

Страница 28: ...gitofan optionSEGyouwill change Theunitdigitofan optionSEGyouwill change Changedvalue Indication 0 D 2 1 7 1 When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status If you are using heat pump model mixed operation mode two or more indoor units op...

Страница 29: ... Communicationerrorbetweenindoorunits EEPROMerror EEPROMoptionerror Erroroftemperaturesensorinindoorunit open short ErrorofoutdoorUnit Self Diagnosis Erroroftheindoorunitpipesensor Highpressureblockageerror Indoorfanerror Thermalfuseopenerror IndoorunitfloatS W2nddetection On Flickering XOff f f If you turn off the air conditioner when the LED is flickering the LED is also turned off f f Ifyoure o...

Страница 30: ...outdoorunitinv mainmicom ForPF 4 6controller errorwillbedeterminedfromthetimewhencompressoristurnedon E221 Erroronoutdoortemperaturesensor ShortorOpen E231 ErroronoutdoorCONDOUTsensor ShortorOpen E251 Errorondischargetemperaturesensorofcompressor1 ShortorOpen E320 ErroronOLPsensor ShortorOpen E403 Compressordownduetofreezeprotectioncontrol E404 Systemstopduetooverloadprotectioncontrol E416 Systems...

Страница 31: ...ror E474 ErroronIPMHeatSinksensorofinverter1 ShortorOpen E475 Erroroninverterfan2 E484 PFCOverload Overcurrent Error E485 Erroroninputcurrentsensorofinverter1 ShortorOpen E500 IPMoverheaterroroninverter1 E508 Smartinstallisnotinstalled E554 Gasleakdetected E556 Errorduetomismatchingcapacityofindoorandoutdoorunit E557 DPMremotecontrolleroptionerror E590 InverterEEPROMCheckSumerror E660 InverterBoot...

Страница 32: ...forindoorand outdoorunits refertotheinstallationmanual CAUTION Unit mm 120 60 20 20 20 180 Powercable providedbyus 20 Wiretubepowercable 3 Insertbothsidesofcorewireofthepowercableintotheconnectionsleeve f f Method1 Pushthecorewireintothesleevefrombothsides Connectionsleeve f f Method2 Twistthewirecorestogetherandpushitintothesleeve Connectionsleeve 4 Usingacompressor compressthetwopointsandflipito...

Страница 33: ...ontube 7 Aftertubecontractionworkiscompleted wrapitwiththeinsulationtapetofinish Makesurethattheconnectionpartsarenotexposedtooutside Besuretouseinsulationtapeandacontractiontubemadeofapprovedreinforcedinsulatingmaterialsthathavethe samelevelofwithstandvoltagewiththepowercable Complywiththelocalregulationsonextensions CAUTION Insulationtape Incaseofextendingtheelectricwire pleaseDONOTusearound sha...

Страница 34: ......

Страница 35: ...rconditioner Installation manual AM JNCD Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it forfuture reference DB68 06702A 03 ...

Отзывы: