background image

Air conditioner

Installation manual

AM***BN4PCH***

 

• Thank you for purchasing this Samsung air conditioner.

 

• Before operating this unit, please read this manual carefully and retain it for future reference.

DB68-11686A-00_IM_DVM 고효율 Wind Free 4way_AA_EN.indd   1

DB68-11686A-00_IM_DVM 고효율 Wind Free 4way_AA_EN.indd   1

2022-02-14   오전 10:11:28

2022-02-14   오전 10:11:28

Содержание AM BN4PCH Series

Страница 1: ...ng this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference DB68 11686A 00_IM_DVM Wind Free 4way_AA_EN indd 1 DB68 11686A 00_IM_DVM...

Страница 2: ...assembly pipes to the refrigerant pipes 10 Step 8 Performing the gas leak test 11 Step 9 Insulating the refrigerant pipes 11 Step10 Installing the drain hose and drain pipe 12 Step11 Performing the dr...

Страница 3: ...orwhich it has been designed the indoorunit is not suitable to be installed in areas used forlaundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the po...

Страница 4: ...eration of any other domestic appliance connected to the same electric lines Always verify that the cut off and protection switches are suitably dimensioned Verify that the airconditioneris connected...

Страница 5: ...is not touchable by users Rigid wall without vibration Where it is not exposed to direct sunshine Where the airfilter can be removed and cleaned easily Do not install the airconditionerin following pl...

Страница 6: ...36 60 11 89 302 9 33 237 12 99 330 2 17 55 2 17 55 1 61 41 2 80 71 5 24 133 7 32 186 Model AM006BN4PCH AM009BN4PCH AM012BN4PCH AM018BN4PCH AM024BN4PCH AM030BN4PCH AM036BN4PCH AM048BN4PCH Chassis Medi...

Страница 7: ...lating the bodyof the indoorunit If you install a cassette type indoor unit on the ceiling when temperature is over 80 6 F 27 C and humidity is over 80 you must apply an extra10 mm thick polyethylene...

Страница 8: ...th of each attached suspension bolt If the length of the suspension bolt is more than 4 92 ft 1 5 m you are required to prevent vibration 4 Screw eight pairs of nuts and washers to the suspension bolt...

Страница 9: ...ake sure that you have the required tools available pipe cutter reamer flaring tool and pipe holder 2 If you wish to shorten the pipes cut them with a pipe cutter ensuring that the cut edge remains at...

Страница 10: ...3 Cut off any excess foam insulation 4 Make sure that there are no cracks orwaves on the bent area 5 It would be necessary to double the insulation thickness 0 39 inch 10 mm ormore to prevent condens...

Страница 11: ...e avoiding compressing the insulation too much Insulation cover pipe Insulation pipe Besuretooverlaptheinsulation Indoor unit CAUTION Be sure to wrap insulation tightlywithout any gaps 3 Finish wrappi...

Страница 12: ...gs frequently exposed to moisture and cooling are not covered For example pipes installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently Places where the pipe...

Страница 13: ...hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to a wall frame or other support as close to the unit as possible Support pieces 1 to 1 5 m 1 100 or...

Страница 14: ...e hose and the drian pipe is used CAUTION The leak test must be performed for at least 24 hours 2 Check the condensed water drainage a Pour about 2 liters of water into the indoor unit drain pan as sh...

Страница 15: ...many indoor units are connected from one breaker Connect F3 F4 for communication to the communication cable of the wired remote control Tighten the electric wires with a propertool within the torque l...

Страница 16: ...g based on the norminal dimension of the power cable 2 Coverthe connection part of the power cable and crimping terminal lug to insulate it Silver solder F E L D d1 B d 2 t B 2 R Outdoor Unit Wired Re...

Страница 17: ...oltage V 1000 Ak k 1 NOTE Coef 1 55 Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Norminal dimensions forcable inch mm Norminal dimensions for...

Страница 18: ...3mm You must keep the cable in a protection tube Maximum length of power cables are decided within 10 of power drop If it exceeds you must consider another power supplying method The circuit breaker M...

Страница 19: ...surfaces of the wires copperwires overa long time This may cause an increase of resistance reduction of passing current and consequently may result in a fire 4 Using a crimping tool compress the two p...

Страница 20: ...on the model 1 Enterthe mode for setting the options a Remove the batteries from the remote control and then insert them again b While holding down the High Temp and Low Temp buttons simultaneously i...

Страница 21: ...3 Set the SEG4 and SEG5 values a Set the SEG4 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG4 b Set the SEG5 value by pressi...

Страница 22: ...you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the following order SEG10 8 Press the Mode button Heat and On appear on the remote...

Страница 23: ...on the remote control display SEG16 b Set the SEG17 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or...

Страница 24: ...f appear on the remote control display 19 Set the SEG23 and SEG24 values a Set the SEG23 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control d...

Страница 25: ...nnected to the indoor unit so that it can receive options Indoorunit Indoorunit 3 Set an address MAIN RMC MCU port for each indoor unit using the remote control according to your air conditioning syst...

Страница 26: ...the indoor unit maintains previous RMC address although you enterthe option value forthe SEG11 or SEG12 You cannot set the SEG11 or SEG12 to F value at the same time If the indoor unit is connected to...

Страница 27: ...alue otherthan 2 and 6 it is automatically set to 2 1000 hours If you set an option to a value that is out of range specified above the option is automatically set to 0 by default The SEG5 option Use...

Страница 28: ...oling 2 4 Use 10min 1 6 Disuse Use Heating Cooling 2 1 Use 7 Use Use Heating Cooling 2 8 Disuse Use CoolingUltra LowFan 2 2 Highceiling KIT 4way modelonly 6 Use 30min 1 9 Use Use CoolingUltra LowFan 2...

Страница 29: ...DSKitinstallation option Indicationand Details Indication Details Indication Details Indication Details Indication Details Indication Details HeatingSetting Compensation RemovingCondensate WaterinHeat...

Страница 30: ...conditioner operates the heating mode immediately afterfinishing the cooling mode the condensate water in the drain pan becomes watervapor by the heat of the indoor unit heat exchanger Since the water...

Страница 31: ...G7 SEG8 SEG9 SEG10 SEG11 SEG12 1 When setting SEG3 Standard formode change Cooling Heating When setting SEG3 Time required for mode change Compensation option forLong pipe orheight difference between...

Страница 32: ...4 3 6 2 0 4 5 4 3 0 2 Use Cooling onlyindoor unitforHR 5 4 5 2 5 5 4 5 2 5 5 6 3 3 5 6 5 4 3 0 6 5 4 3 0 6 7 2 4 0 7 6 3 3 5 7 6 3 3 5 7 8 1 4 5 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PA...

Страница 33: ...utes Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Explanation PAGE Forcing FAN Operation forHeating and Cooling Indication and Details Indication Details Indication Details Cooling Fan Setting Heating F...

Страница 34: ...ned on when the temperature is maintained as 8 1 F 4 5 C for10 minutes Room temp set temp f heating compensation temp External heater is turned off when the temperature is maintained as 8 1 F 4 5 C 1...

Страница 35: ...o 9 New value 0 to F Example Changing the Buzzer control SEG17 option of the installation options to1 disuse Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Function Page Mode Type of the option to change Tens p...

Страница 36: ...erfinishing the installation of the airconditioner you should explain the following to the user Referto appropriate pages in the User s Manual 1 How to start and stop the air conditioner 2 How to sele...

Страница 37: ...indoor outdoorunits for2 minutes E101 X X 2 Communication errorreceived from the outdoorunit E102 3 3 miniute tracking erroron outdoorunit E202 4 Communication erroraftertracking due to unmatching nu...

Страница 38: ...control_1 E410 14 Simultaneous opening of cooling heating MCU SOLvalve 1st detection E180 15 Simultaneous opening of cooling heating MCU SOLvalve 2nd detection E181 Otheroutdoorunit self diagnosis err...

Страница 39: ...Model Charging additional refrigerant kg lb AM006BN4PCH AM009BN4PCH AM012BN4PCH 0 6 1 32 AM018BN4PCH AM024BN4PCH 0 73 1 61 AM030BN4PCH AM036BN4PCH AM048BN4PCH 0 88 1 94 DB68 11686A 00_IM_DVM Wind Fre...

Страница 40: ...DB68 11686A 00_IM_DVM Wind Free 4way_AA_EN indd 40 DB68 11686A 00_IM_DVM Wind Free 4way_AA_EN indd 40 2022 02 14 10 11 36 2022 02 14 10 11 36...