55
English
Instal
lation Pr
oc
edur
e
Optional item
Input unit
SEG1
SEG2
SEG3
SEG4
Function of the option
Remarks
Silent mode
Main
0
7
0
0
Disabled (Factory default)
Enables the silent mode for night-
time in cooling mode (It operates
automatically depending on the
temperature.)
However, if the external contact
interface module (MIM-B14) is used,
entering the silent mode is available
with contact signal in cooling and
heating mode.
0
1
LEVEL 1 / Auto
0
2
LEVEL 2 / Auto
0
3
LEVEL 3 / Auto
0
4
LEVEL 1 / External contact
0
5
LEVEL 2 / External contact
0
6
LEVEL 3 / External contact
0
7
LEVEL 1
0
8
LEVEL 2
0
9
LEVEL 3
High-head condition
setting
Main
0
8
0
0
Disabled (Factory default)
0
1
Level 1 of height difference type 1
(Indoor unit is lower than outdoor
unit)
When outdoor unit is located
40~80m above the indoor unit
0
2
Level 2 of height difference type 1
(Indoor unit is lower than outdoor
unit)
When outdoor unit is located over
80m above the indoor unit
0
3
Height difference type 2 (Outdoor
unit is lower than indoor unit)
When indoor unit is over 30 m above
the outdoor unit
Long-piping
condition setting
Main
0
9
0
0
Disabled (Factory default)
0
1
LEVEL 1
When equivalent length of farthest
indoor unit from the outdoor unit is
between 100~170m
0
2
LEVEL 2
When equivalent length of farthest
indoor unit from the outdoor unit is
over 170m
Energy control
operation
Main
1
0
0
0
Basic (Factory default)
Energy control option of designated
operation sequence
Operating in energy saving mode,
capacity might decrease compared to
normal operation mode
0
1
Energy saving
0
2
Power
Rotation defrost
(HR only)
Main
1
1
0
0
Disabled (Factory default)
0
1
Enabled
When enabled, continuous heating
operation is possible but heating
performance will decrease during
rotation defrost operation
Expand operational
temperature range
for cooling operation
(HR only)
Main
1
2
0
0
Disabled (Factory default)
0
1
Enabled
When enabled, continuous cooling
operation is possible even in low
temperature condition up to -15°C,
but noise of the MCU will increase
Channel address
Main
1
3
A
U
Automatic setting (Factory default)
Address for classifying the product
from upper level controller (DMS,
S-NET 3, etc.)
0 ~ 15
Manual setting for channel 0~15
Snow accumulation
prevention control
Main
1
4
0
0
Enabled (Factory default)
During snow accumulation, the fan
may spin even when the unit is not
in operation
0
1
Disabled
Unused option
Main
1
5
0
0
Unused option
Unused option by this model
Unused option
Main
1
6
0
0
Unused option
Unused option by this model