Samsung AJ100FCJ5 Series Скачать руководство пользователя страница 18

18

A

High Temp Button

High Fan Button

Mode change

Low Temp Button

Low Fan Button

Entering mode for 

setting option

Option setting mode

  Setting option

 

1.  Remove batteries from the remote controller.

2.  Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button.  

3.  Each time you press  Low Fan button, 7-seg on left side is increased by “1” and each time you press High Fan button,  

 

  7-seg on right side is increased by “1”. 
4.  You press 

 button to move to the next setteing page.  

 

5.  After setting option, press 

 button to check whether the option code you input is correct or not.

 

6.  Press operation button 

 with the direction of remote control for set.

•    SEG1, SEG7, SEG13, SEG19 are not set as page option.
•  Set the SEG1, SEG7 as ON status and SEG13, SEG19 as OFF status.
  EX) Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting   

    option at the same time.

Setting option 

(AQV**/AJN**/AR**)

Setting indoor unit address manually

Setting indoor unit address 

RJ100F5HXEA_IM_E_32978A(4).indd   18

2012-10-25   오후 5:22:49

www.keveklima.hu

Содержание AJ100FCJ5 Series

Страница 1: ...ank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register DB98 32978A 4 S E F I P D G RJ100F5HX AJ100FCJ5 RJ100F5HXEA_IM_E_32978A 4 indd 31 2012 10 25 오후 5 22 56 w w w k e v e k l i m a h u ...

Страница 2: ...always carefully read the following warnings Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air conditioner is sold or transferred This manual explains how to install an indoor unit with a split system with two SAMSUNG units The use of other types of units with different control systems may damage the units and invalidate the war...

Страница 3: ...ubstances or close to equipment that release free flames to avoid the occurrence of fires explosions or injuries To prevent injury when accidentally touching the indoor unit fan install the indoor unit at least 2 5m above the floor The air conditioner should be used only for the applications for which it has been designed the indoor unit is not suitable to be installed in areas used for laundry Ou...

Страница 4: ... are not supplied use the standard cable approved by IEC standard Please check Method for connecting wires section 3 wire Power Cable option 2 wire Assembly Cable option Drain Plug Installation Manual Rubber Leg Flare Nuts 15 88mm outer pipe diameter Flare Nuts 9 52mm outer pipe diameter Tube connector Pipe 12 70mm Bolt 9 52mm Tube connector Pipe 12 70mm Bolt 15 88mm Energy Label RJ100F5HXEA_IM_E_...

Страница 5: ...tdoor unit so that the air flow is directed towards the outside as indicated by the arrows on the top of the unit Maintain sufficient clearance around the outdoor unit as indicated in page 8 Make sure that the water dripping from the drain hose runs away correctly and safely Outdoor Unit You have just purchased a Free Joint Multi air conditioner and it has been installed by your installation speci...

Страница 6: ...or more 2000 or more The upper part of the outdoor unit and the air outlet is towards the wall 1500 or more 600 or more 300 or more The upper part of the outdoor unit and the air outlet is opposite the wall 300 or more When front and rear side of the outdoor unit is towards the wall Unit mm When installing more than 1 outdoor unit Unit mm When the air outlet is towards the wall 1500 or more RJ100F...

Страница 7: ...e in the noise level and vibration particularly if the outdoor unit is to be installed close to a neighbour If it is to be installed in a location exposed to strong winds or at a height the unit must be fixed to an appropriate support wall or ground 620mm 360mm Rubber leg 300 or more 300 or more 1500 or more 600 or more 3000 or more 300 or more 3000 or more 600 or more 600 or more 300 or more 1500...

Страница 8: ...nd vibration Indoor unit Outdoor unit Power supply ø V Hz 020 023 026 030 035 052 07 09 12 18 24 RJ100F5HX AJ100FCJ5 1 220 240 50 60 Unit Outside diameter Liquid Gas 020 023 026 030 035 07 09 12 1 4 3 8 052 18 1 2 24 5 8 1 Room max length 5 Room total max length Max height between indoor unit outdoor unit Max height between indoor units Dimension 25m 80m 15m 7 5m Composition A B C D E A B C D E H ...

Страница 9: ... to the outdoor unit and purge the circuit refer to page 10 While heating ice may accumulate During the process of defrosting check if condensation draining is adequate For adequate draining do the following 1 Insert the drain plug into the drain hole on the underside of the outdoor unit 2 Connect the drain hose to the drain plug 3 Ensure that condensation draining is adequate Drain hole Drain hol...

Страница 10: ...4 Purge the air from the system using vacuum pump for about 30 minutes Close the valve of the low pressure side of manifold gauge clockwise Make sure that pressure gauge show 0 1MPa 76cmHg after about 30 minutes This procedure is very important in order to avoid gas leak Turn off the vacuum pump Remove the hose of the low pressure side of manifold gauge 5 Set valve cork of both liquid side and gas...

Страница 11: ...checkedforleakageatleastonceevery12months ac cordingtoregulationN 842 2006 Thisactivityhastobecoveredbyqualified personnelonly Incasesituationabove 3kgormoreofR 410A installer orrecognisedperson whichhasresponsabilityforfinalcheck hastoprovidea maintenancebook withalltheinformationrecordedaccordingto REGULATION EC N 842 2006OFTHEEUROPEANPARLIAMENTANDOFTHE COUNCILof17May2006oncertainfluorinatedgree...

Страница 12: ... system on in cooling with fan operating at high velocity Compressor will immediately start provided 3 minutes have elapsed since the last stop 3 After 2 minutes of operation shut off the suction valves with the allen wrench 4 Turn the system off and switch mains supply off 5 Disconnect pipes After disconnection protect valves and tubing ends from dust 6 Compressor damage may occur if run at a neg...

Страница 13: ...unication Cable Specification 2G 0 75mm2 or more Abbreviations MCA Min Circuit Amps A MFA Max Fuse Amps A 1 L 2 N 1 L 2 N A B 1 L 2 N F1 F2 1 L 2 N F1 1 L 2 N F1 1 L 2 N F1 F2 1 2 F1 F2 F1 F2 1 2 2 1 F2 1 2 F1 F2 F1 F2 F2 F1 F2 F1 F2 1 2 1 2 1 2 B C B C B C B C A 1 L 2 N F1 F2 F1 F2 F1 F2 1 2 B C 1 L 2 N 1 L 2 N 1 L 2 N F1 F2 F1 F2 F1 F2 F1 F2 L N 1 2 2 1 2 1 C B D Earth terminal Earth terminal Ea...

Страница 14: ...ith staples If the earthing electrode is installed in an area of heavy traffic its wire must be connected securely j 5 Carefully check the installation by measuring the earthing resistance with an earthing resistance tester If the resistance is above the required level Example 100Ω drive the earthing electrode deeper into the ground or increase the number of earthing electrodes 6 Connect the earth...

Страница 15: ...t connected to refrigerant pipe A The outdoor unit is communicating correctly with the indoor unit connected to refrigerant pipe B The outdoor unit is communicating correctly with the indoor unit connected to refrigerant pipe C The outdoor unit is communicating correctly with the indoor unit connected to refrigerant pipe D The outdoor unit is communicating correctly with the indoor unit connected ...

Страница 16: ...tdisplayofoutdoorunitdisplayPCB DIS01 willcountfrom00 01 02to15 Estabilishedcommunicationtheleftdisplaywillcountsequentially 00 communicationwithindoorunitA 01 communicationwithindoorunitB 02 communicationwithindoorunitC 03 communicationwithindoorunitD 04 communicationwithindoorunitE IncaseofManualaddressmode youcandopipecheckoperationforcheckwhetheryouconnectthepipescorrectlyornot Butyouneedsetin...

Страница 17: ...O SET ADDRESSING MANUALLY BY ROTARY SWITCH SW02 RAC MH020FV N A MH023FB MH026FB V N A MH035FB V N A MH052FB V N A IT S HERE sw02 MAIN PCB SLIM 1 WAY CASSETTE MH026FS MH035FS sw02 MINI 4 WAY CASSETTE MH030FM MH035FM MH052FM sw02 sw02 SLIM DUCT MSP DUCT MH026FE MH035FE NJ026LHX NJ035LHX MH052FU sw02 CONSOLE MH026FJ MH035FJ MH052FJ MAIN PCB RJ100F5HXEA_IM_E_32978A 4 indd 17 2012 10 25 오후 5 22 48 w w ...

Страница 18: ...by 1 4 You press button to move to the next setteing page 5 After setting option press button to check whether the option code you input is correct or not 6 Press operation button with the direction of remote control for set SEG1 SEG7 SEG13 SEG19 are not set as page option Set the SEG1 SEG7 as ON status and SEG13 SEG19 as OFF status EX Set the each option separately since you cannot set the ADDRES...

Страница 19: ...ton to enter SEG12value Step 7 Press Mode button to be changed to AUTO mode in the OFF status 1 Press Fan button to enter SEG14 value 2 Press High Fan button to enter SEG15 value Step 8 Press Mode button to be changed to Cool mode in the OFF status 1 Press Low Fan button to enter SEG16 value 2 Press High Fan button to enter SEG17 value Step 9 Press Mode button to be changed to DRY mode in the OFF ...

Страница 20: ...it address 10 digit of indoor unit A single digit of indoor unit Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A single digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Setting RMC address ...

Страница 21: ... the option value of SEG4 6 If you set the SEG 9 as 0 the indoor unit will maintain previous RMC ADDRESS even if you input the option value of SEG11 12 5 The MAIN address is for commnication between the indoor unit and the outdoor unit Therefore you must set it to operate the air conditioner properly RJ100F5HXEA_IM_E_32978A 4 indd 21 2012 10 25 오후 5 22 50 w w w k e v e k l i m a h u ...

Страница 22: ...mber of electric and electronics loads consumption and use Ampere limits switch DIP Switch just as emergency solution or in case the system is anyway oversized compared to real thermal load needed Ampere Limit Switch DIP Switch is initially set to the default value table below Ampere Limit Switch DIP Switch is on the PCB of outdoor unit Contact the authorized service technician or dealer for setti...

Страница 23: ...Explanation Push Display Explanation 0 Present Compressor Frequency 8 Discharge temperature 1 Target Compressor Frequency 9 OLP temperature 2 EEV0 current step 10 Condenser temperature 3 EEV1 current step 11 Outdoor temperature 4 EEV2 current step 12 Running current 5 EEV3 current step 13 Target Discharge temperature 6 EEV4 current step 14 Total capacity of the indoor units 7 Fan RPM H high L low ...

Страница 24: ...units refer to page 26 5 Assemble a cover of the outdoor unit and turn the power on 6 Check the communication status 7 If you install a transmitter to the outdoor unit every indoor unit which is connected to the outdoor unit can be controlled simulta neously 8 Each outdoor unit connected to the same centralized controller has its own transmitter 9 When using the centralized controller refer to pag...

Страница 25: ...PCB as seen in the picture 5 Connect the wire remote controller central remote controller etc to the sub PCB 6 Assemble the panel frame and the front panel The product and accessories may look different from the illustration above depending on the model If indoor unit is AQV AR install sub PCB Sub PCB Sub PCB installation optional RJ100F5HXEA_IM_E_32978A 4 indd 25 2012 10 25 오후 5 22 53 w w w k e v...

Страница 26: ...ave Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 0 0 0 0 Slave 1 Master Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation PAGE Externalcontrol Externalcontroloutput Buzzer Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication ...

Страница 27: ...fan motor can remain off to avoid cold air blown into conditioned space Before leaving the premises on which you have installed the air conditioner you should explain the following operations to the owner making reference to appropriate pages in the owner s instruction booklet 1 How to start and stop the air conditioner 2 How to select the operating mode and adjust the temperature and fan settings...

Страница 28: ...installationthroughautoaddressingmodewithoutpipecheckoperation Check setting The number of Indoor unit mismatched Check electrical connection and setting Communication error between the outdoor and indoor unit Check electrical connection and setting Outdoor communication error between main micom and inverter micom Outdoor communication error beween main micom and hub micom Outside temperature sens...

Страница 29: ...lf diagnosis Outdoor unit EEV open operating indoor unit s Self diagnosis High temperature over 30 C of outdoor as heating mode Low temperature under 10 C of outdoor as cooling mode Outdoor Fan Error Communication cable mismatched between indoor and outdoor unit Check electrical connection Inverter compressor starting failure 5 times Compressor trip by input current control mode PFC over current C...

Страница 30: ... EEE Yönetmeliğine Uygundur This EEE is compliant with RoHS RJ100F5HXEA_IM_E_32978A 4 indd 30 2012 10 25 오후 5 22 55 w w w k e v e k l i m a h u ...

Страница 31: ...conditions kW 3 0 3 0 3 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refrigerant fluid would...

Страница 32: ...kW 4 3 5 5 5 8 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refrigerant fluid would be leaked ...

Страница 33: ...ns kW 5 8 7 7 7 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refrigerant fluid would be leak...

Страница 34: ...t reference design conditions kW 3 7 5 8 4 3 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refr...

Страница 35: ... conditions kW 5 8 7 7 5 8 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refrigerant fluid woul...

Страница 36: ...sign conditions kW 5 8 7 7 3 0 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refrigerant fluid ...

Страница 37: ...t reference design conditions kW 3 7 5 8 3 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refr...

Страница 38: ...erence design conditions kW 3 7 5 8 3 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refrigera...

Страница 39: ...kW 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to the atmosphere This appliance contains a refrigerant fluid with a GWP equal to 1975 This means that if 1 kg of this refrigerant fluid would be leaked to the atmosphere the impact on global warming woul...

Страница 40: ...té énergétique SCOP K Classe di efficienza energetica SCOP L QHE 3 temporada calefacción L QHE 3 saison chaude L QHE 3 stagione di riscaldamento M Otras temporadas de calefacción declaradas aptas para funcionar M Adapté à d autres saisons chaudes M Altre stagioni per uso in riscaldamento N Pdesignh promedio N Pdesignh moyenne N Pprogrisc Climi Medi O Pdesignh más cálida O Pdesignh plus chaud O Ppr...

Страница 41: ...Εποχιακός Συντελεστής Απόδοσης SCOP K Classe de eficiência energética SCOP K Energieeffizienzklasse SCOP K Κλάση ενεργειακής επάρκειας SCOP L QHE 3 estação de aquecimento L QHE 3 Heizperiode L QHE 3 εποχή θέρμανσης M Outras estações de aquecimento utilizáveis M Weitere geeignete Heizperioden M Κατάλληλο για χρήση σε άλλες εποχές θέρμανσης N Pdesignh média N Pdesignh mittel N Pdesignh μέσο O Pdesig...

Страница 42: ...mais d interférer avec le circuit de fluide frigorigène ou de démonter le produit vous même et demandez toujours conseil à un professionnel 2 Consommation énergétique XYZ kWh par an basée sur des résultats de tests standard La consommation énergétique réelle dépend de la méthode d utilisation de l appareil et de sa situation géographique 3 Consommation énergétique XYZ kWh par an basée sur des résu...

Страница 43: ...Jahren 1975 Mal höher wäre als bei 1 kg freigesetztem CO2 Versuchen Sie niemals selbst den Kühlkreislauf zu unterbrechen oder das Gerät auseinanderzubauen Wenden Sie sich stets an die entsprechenden Fachleute 2 Energieverbrauch von XYZ kWh pro Jahr ausgehend von Standardtestergebnissen Der tatsächliche Energieverbrauch hängt von der Art derVerwendung sowie dem Aufstellungsort des Geräts ab 3 Energ...

Страница 44: ...14 Memo RJ100F5HXEA_IM_Product fiche_32978A 4 indd 14 2012 11 12 오후 3 59 56 w w w k e v e k l i m a h u ...

Отзывы: