Step 8  Performing the gas leak test

To identify potential gas leaks on the indoor unit, inspect 

the connection area of each refrigerant pipe using a leak 

detector for R-410A.

Before recreating the vacuum and recirculating the 

refrigerant gas, pressurize the whole system with 

nitrogen (using a cylinder with a pressure reducer) at a 

pressure above 0.2 MPa, less than 4 MPa (gauge) in order 

to immediately detect leaks on the refrigerant fittings.

Made vacuum for 10 minutes and pressurizing system 

with nitrogen.

Liquid side

Gas side

Insulator

Step 9  Insulating the refrigerant pipes

Once you have checked that there are no leaks in the 

system, you can insulate the piping and hose.

To avoid condensation problems, place Acrylonitrile 

Butadien Rubber separately around each refrigerant pipe.

No gap

NBR

  NOTE

• 

Always make the seam of pipes face upwards.

Wind insulating tape around the pipes and drain hose 

avoiding compressing the insulation too much.

Insulation cover pipe
Insulation pipe

Be sure to overlap the insulation.

Indoor unit

  CAUTION

• 

Be sure to wrap insulation tightly without any gaps.

Finish wrapping insulating tape around the rest of the 

pipes leading to the outdoor unit.

The pipes and electrical cables connecting the indoor 

unit with the outdoor unit must be fixed to the wall 

with suitable ducts.

  CAUTION

•  Make sure that all refrigerant connection must be 

accessible for easy maintenance and detachment.

• 

Install the insulation not to get wider and use the 

adhesives on the connection part of it to prevent 

moisture from entering.

• 

Wind the refrigerant pipe with insulation tape if it is 

exposed to outside sunlight.

• 

Install the refrigerant pipe respecting that the 

insulation does not get thinner on the bent part or 

hanger of pipe.

• 

Add the additional insulation if the insulation plate 

gets thinner.

a x 3

Hanger

Additional insulation

a

Refrigerant pipe 

insulation

Select the insulation of the refrigerant pipe.

•  Insulate the gas side and liquid side pipe, noting 

the insulation thickness that must differ according 

to the pipe size.

• 

Standard: Less than an indoor temperature 

of 30°C, with humidity at 85%. If installing in 

a high humidity environment, use one grade 

thicker insulator by referring to the table below. 

If installing in an unfavourable environment, use 

thicker one.

• 

The heat-resistance temperature of the insulator 

must be more than 120°C.

Содержание AJ052NBNDEH/SA

Страница 1: ...Airconditioner Usermanual AJ NBNDEH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this user manual carefully and retain it for future reference...

Страница 2: ...nd preparing accessories Step 2 Choosing the installation location Step 3 Optional Insulating the body of the indoor unit Step 4 Installing the indoor unit Step 5 Purging inert gas from the indoor uni...

Страница 3: ...t or human health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household u...

Страница 4: ...azards or unsafe practices that may result in severe personal injury or death CAUTION Hazards or unsafe practices that may result in minor personal injury or property damage Follow directions Do NOT a...

Страница 5: ...not install this appliance in a humid oily ordusty location in a location exposed to direct sunlight and water rain drops Do not install this appliance in a location where gas may leak This may result...

Страница 6: ...eating operation in the outdoor unit may overflow and result in property damage In particular in winter if a block of ice falls it may result in injury death or property damage FOR POWER SUPPLY WARNIN...

Страница 7: ...tioner please contact yournearest service centre Failing to do so may result in problems with the product water leakage electric shock or fire A delivery service for the product is not provided If you...

Страница 8: ...inserting their fingers into the product Do not strike orpull the airconditionerwith excessive force This may result in fire injury or problems with the product Do not place an object nearthe outdooru...

Страница 9: ...or injury Do not operate the appliance with wet hands This may result in electric shock Do not sprayvolatile material such as insecticide onto the surface of the appliance As well as being harmful to...

Страница 10: ...oloration deformation damage electric shock or fire Before cleaning orperforming maintenance unplug the airconditioner from the wall socket and wait until the fan stops Failing to do so may result in...

Страница 11: ...03 01 01 Display 02 Airflow blade Airoutlet inside Wind Free panel You can use the Wind Free Cooling function when the Cool Dry orFan mode is running Referto the remote control manual for product ope...

Страница 12: ...erwill stop Dry mode 18 C to 32 C Condensation may occur on the indoor unit with risk to have eitherwater blow off or drop on the floor CAUTION If you use the air conditioner at a relative humidity ab...

Страница 13: ...r organic solvents such as thinner kerosene and acetone to clean the surfaces Do not attach any stickers on the surfaces because this may cause damage When you clean the heat exchanger on the indoor u...

Страница 14: ...filter from the indoor unit 2 Cleaning the air filter Clean the air filterwith a vacuum cleaner or soft brush If dust is too heavy then rinse it with running water and dry it in a ventilated area CAU...

Страница 15: ...e control Press the Filter Reset button Indoor unit with the wireless remote control Press the Options button or Filter Reset Blinking press the SET button NOTE The filter reset indicator blinks when...

Страница 16: ...nths Required Replace the remote control batteries At least once a year Outdoor unit Clean the heat exchanger on the outside of the unit Once every 4 months Required Clean the heat exchanger on the in...

Страница 17: ...ange the set temperature Press the Temperature button to decrease or increase the temperature Check if the air filter is blocked by dirt Clean the air filter every two weeks Check if the air condition...

Страница 18: ...s not working Check if your batteries are depleted Make sure batteries are correctly installed Make sure nothing is blocking your remote control sensor Check that there are strong lighting apparatus n...

Страница 19: ...ions forwhich it has been designed the indoor unit is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch the unit off and disconnect it fro...

Страница 20: ...nected to the same electric lines Always verify that the cut off and protection switches are suitably dimensioned Verify that the air conditioner is connected to the power supply in accordance with th...

Страница 21: ...e chosen location is well drained The indoor unit must be installed such that it is beyond public access and is not touchable by users Do not install the airconditionerin following places Place where...

Страница 22: ...ot applicable to Wind Free models 580 585 Celling opening 500 Suspension position 580 585 Celling opening 500 Suspension position 620 620 Model AJ016NBNDEH AJ020NBNDEH AJ026NBNDEH AJ035NBNDEH AJ052NBN...

Страница 23: ...door unit to avoid the possibility of breakage You must hold the hanger plate on the corner and carry the indoor unit Step 3 Optional Insulating the bodyof the indoorunit If you install a cassette typ...

Страница 24: ...sion bolt If the length of the suspension bolt is more than 4 9 ft 1 5 m you are required to prevent vibration 4 Screw eight pairs of nuts and washers to the suspension bolts making space for hanging...

Страница 25: ...nd pipe holder 2 If you wish to shorten the pipes cut them with a pipe cutter ensuring that the cut edge remains at a 90 angle to the side of the pipe Refer to the illustrations below for examples of...

Страница 26: ...floor and to improve the efficiency of the unit 3 Cut off any excess foam insulation 4 Make sure that there are no cracks orwaves on the bent area 5 It would be necessary to double the insulation thi...

Страница 27: ...n tightlywithout any gaps 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 The pipes and electrical cables connecting the indoor unit with the outdoor unit...

Страница 28: ...rmitory and studio or near an exit that opens and closes frequently Places where the pipes are installed that are highly humid due to a lack of ventilation Step10 Installing the drain hose and drain p...

Страница 29: ...Under gradient Ceiling Do not apply force to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to...

Страница 30: ...ly in the Cool mode you can check the correct operation of the drain pump When the electric cable connection has not been completed Remove the control box cover of the indoor unit Connect the power su...

Страница 31: ...Route the connection cord through the side of the indoor unit and connect the cable to the terminals refer to the figure below 3 Route the other end of the cable to the outdoor unit through the ceilin...

Страница 32: ...nsider another power supplying method The circuit breaker MCCB ELB should be considered more capacity if many indoor units are connected from one breaker Use round pressure terminal for connections to...

Страница 33: ...th the insulation tape twice or more and position your contraction tube in the middle of the insulation tape Three or more layers of insulation are required Method 1 Method 2 Insulation tape 35 mm 40...

Страница 34: ...High Temp and Low Temp buttons simultaneously insert the batteries into the remote control c Make sure that you are entered to the mode for setting the options 2 Set the option values CAUTION The tota...

Страница 35: ...e SEG4 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG4 b Set the SEG5 value by pressing the High Fan button repeatedly until...

Страница 36: ...ontrol display When you press the Low Fan or High Fan button values appear in the following order SEG10 8 Press the Mode button Heat and On appear on the remote control display 9 Set the SEG11 and SEG...

Страница 37: ...the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG16 b Set the SEG17 value by pressing the High Fan button repeatedly until the value you want to...

Страница 38: ...you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the following order SEG22 18 Press the Mode button Heat and Off appear on the remot...

Страница 39: ...Power button again 5 Check whether the air conditioner operates in accordance with the option values you have set a Reset the indoor unit by disconnecting and then reconnecting the power cable of the...

Страница 40: ...igit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation Page Reserved Setting RMC address Reserved Group channel 16 Group address Indication and details Indication Details...

Страница 41: ...e output of external control S Plasma ion BuzzerControl Hours offilterusage SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control with remote control Heating setting compensation offset Dewremoval...

Страница 42: ...SEG11 SEG12 Explanation Page Use of drain pump Reserved Reserved Reserved Remote control Indication and details Indication Details Indication Details Indication Details 1 0 Disuse 0 Slave 1 Use 2 Usew...

Страница 43: ...rved Indication and details Indication Details Indication Details Indication Details Indication Details 3 0 or1 channel1 0 Default 1 0 Default Maintain blade status in windfree mode 2 channel 2 1 2 C...

Страница 44: ...tails 0 D Option type 0 to F Tens position value 0 to 9 Units position value 0 to 9 New value 0 to F Example Changing the Buzzer control SEG17 option of the installation options to 1 disuse Option SEG...

Страница 45: ...ature sensor Error of the discharge temperature sensor X X No communication for 2 minutes between indoor and outdoor unit communication errorfor more than 2 minutes X X Error of outdoor unit Error of...

Страница 46: ...rt CAMBODIA 855 23 993232 1800 20 3232 Toll free www samsung com th support LAOS 856 214 17333 www samsung com th support MALAYSIA 1800 22 8899 HHP 1800 88 9999 OTH 603 7713 7420 Overseas contact www...

Отзывы: