Страница 1: ......
Страница 2: ...le to use it as reference after installation X For maximum safety installers should always carefully read the following warnings X Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air conditioner is sold or transferred XThis manual explains how to install an indoor unit with a split system with two SAMSUNG units The use of other ty...
Страница 3: ...conditioner in environments with hazardous substances or close to equipment that release free flames to avoid the occurrence of fires explosions or injuries XTo prevent injury when accidentally touching the indoor unit fan install the indoor unit at least 2 5m above the floor XThe air conditioner should be used only for the applications for which it has been designed the indoor unit is not suitabl...
Страница 4: ...ion Position the outdoor unit so that the air flow is directed towards the outside as indicated by the arrows on the top of the unit Maintain sufficient clearance around the outdoor unit as indicated in the diagram on the page opposite Make sure that the water dripping from the drain hose runs away correctly and safely You have just purchased a Free Joint Multi air conditioner and it has been inst...
Страница 5: ... It will reduce noise and vibration Indoor unit Outdoor unit Power supply Ø V Hz 020 023 026 035 07 09 12 RJ040F2HX AJ040FCJ2 1 220 240 50 60 Unit Outside diameter Liquid Gas 020 023 026 035 07 09 12 1 4 3 8 RJ040F2HX AJ040FCJ2 Outdoor unit cannot be connected to the following indoor unit combination 052 MH FM A NJ LHXEA 18 24 AJN 1 Room max length 2 Room total max length Max height between indoor...
Страница 6: ...vibration Make at least one round It will reduce noise and vibration Indoor unit Outdoor unit Power supply Ø V Hz 020 023 026 035 052 07 09 12 18 RJ050F2HX AJ050FCJ2 1 220 240 50 60 Unit Outside diameter Liquid Gas 020 023 026 030 035 07 09 12 1 4 3 8 052 18 1 2 RJ050F2HX AJ050FCJ2 Outdoor unit cannot be connected to the following indoor unit combination MH052FMEA MH052FUEA 24 AJN052NDEHA 1 Room m...
Страница 7: ... unit Outdoor unit Power supply Ø V Hz 020 023 026 030 035 052 07 09 12 18 RJ052F3HX RJ060F3HX AJ052FCJ3 AJ068FCJ3 1 220 240 50 60 Unit Outside diameter Liquid Gas 020 023 026 030 035 07 09 12 1 4 3 8 052 18 1 2 1 Room max length 3 Room total max length Max height between indoor unit outdoor unit Max height between indoor units Dimension 20m RJ052F3HXEA 50m RJ060F3HXEA 45m RJ060F3HXEB 50m AJ052FCJ...
Страница 8: ... pipe length It will reduce noise and vibration Make at least one round It will reduce noise and vibration Indoor unit Outdoor unit Power supply Ø V Hz 020 023 026 030 035 052 07 09 12 18 24 RJ070F4HX RJ080F4HX AJ070FCJ4 AJ080FCJ4 1 220 240 50 60 Unit Outside diameter Liquid Gas 020 023 026 030 035 07 09 12 1 4 3 8 052 18 1 2 24 5 8 1 Room max length 4 Room total max length Max height between indo...
Страница 9: ...he outdoor unit are blocked by the wall 1500 or more 2000 or more The upper part of the outdoor unit and the air outlet is towards the wall 1500 or more 600 or more 300 or more The upper part of the outdoor unit and the air outlet is opposite the wall 300 or more When front and rear side of the outdoor unit is towards the wall Unit mm When installing more than 1 outdoor unit Unit mm When the air o...
Страница 10: ...f the outdoor unit are blocked by the wall When front and rear side of the outdoor unit is towards the wall When front and rear side of the outdoor unit is towards the wall When installing more than 1 outdoor unit Unit mm The upper part of the outdoor unit and the air outlet is opposite the wall 300 or more 300 or more 500 or more 500 or more Deciding onWhere to Install the Air Conditioner ...
Страница 11: ...in Plug Installation Manual Rubber Leg Flare Nuts 15 88mm outer pipe diameter RJ080F4HX AJ080FCJ4 Flare Nuts 9 52mm outer pipe diameter Flare Bolt Nut 12 70mm Bolt 9 52mm Flare Bolt Nut 12 70mm Bolt 15 88mm RJ080F 4HX AJ080FCJ4 Energy Label While heating ice may accumulate During the process of defrosting check if condensation draining is adequate For adequate draining do the following 1 Insert th...
Страница 12: ... details on how to connect up to the outdoor unit and purge the circuit refer to page 19 Oblique Rough Burr Outer Diameter D Thickness Depth A ø6 35 mm 1 4 0 8mm 1 3 mm ø9 52 mm 3 8 0 8mm 1 8 mm ø12 70 mm 1 2 0 8mm 2 0 mm ø15 88 mm 5 8 0 8mm 2 2 mm Uneven Thickness Cracked Damaged Surface Inclined Correct 䭭 In case welding the pipe the gas nitrogen must be blown into the parts Connecting the cable...
Страница 13: ...mmunication Cable Specification 2G 0 75mm or more Abbreviations MCA Min Circuit Amps A MFA Max Fuse Amps A Tightening power terminal 䭭 Connect the cables to the terminal board using the compressed ring terminal 䭭 Use rated cables only 䭭 Connect the cables with driver and wrench that can apply the rated torque to the screws 䭭 Make sure that appropriate tightening torque is applied for cable connect...
Страница 14: ...hed flexible cord Code designation IEC 60245 IEC 57 CENELEC H05RN F 2 Select power supply cord based on MCA 3 MFA is used to select the circuit breaker and the ground fault circuit interrupter earth leakage circuit breaker 4 MCA represents maximum input current 5 MFA represents capacity which may accept MCA 6 Communication Cable Specification 2G 0 75mm or more Abbreviations MCA Min Circuit Amps A ...
Страница 15: ... not be lighter than polychloroprene sheathed flexible cord Code designation IEC 60245 IEC 57 CENELEC H05RN F 2 Select power supply cord based on MCA 3 MFA is used to select the circuit breaker and the ground fault circuit interrupter earth leakage circuit breaker 4 MCA represents maximum input current 5 MFA represents capacity which may accept MCA 6 Communication Cable Specification 2G 0 75mm or ...
Страница 16: ...page 17 Upper controller power should be off 4 You must check the position of dip switch on the transmitter s main PCB and the main PCB of MH NJ indoor units For AQV AJN AR indoor units refer to page 30 5 Assemble a cover of the outdoor unit and turn the power on 6 Check the communication status 7 If you install a transmitter to the outdoor unit every indoor unit which is connected to the outdoor ...
Страница 17: ...F2HX RJ050F2HX AJ040FCJ2 AJ050FCJ2 K1 K2 K3 K4 Change DIPswitch K2 on MH NJ indoor units PCB K2 ON OFF For AQV AJN AR indoor units refer to page 30 RJ052F3HX RJ060F3HX RJ070F4HX RJ080F4HX AJ052FCJ3 AJ068FCJ3 AJ070FCJ4 AJ080FCJ4 RJ040F2HX RJ050F2HX AJ040FCJ2 AJ050FCJ2 DC 12V supply Check the dip switch postion on transmitter main PCB as the picture above turn ON DC 12V Blue 1 L 2 N 1 L 2 N F1 F2 F1...
Страница 18: ...lectrodes 6 Connect the earthing wire to the earthing screw on the air conditioner 1 Position the outdoor unit so that the air flow is directed towards the outside as indicated by the arrows on the top of the unit 2 Attach the outdoor unit to the appropriate support using anchor bolts The earthing wire for the telephone line cannot be used to earth the air conditioner 3 DIf the outdoor unit is exp...
Страница 19: ...lose the valve of the low pressure side of manifold gauge clockwise Make sure that pressure gauge show 0 1MPa 76cmHg after about 10 minutes This procedure is very important in order to avoid gas leak Turn off the vacuum pump Remove the hose of the low pressure side of manifold gauge 5 Set valve cork of both liquid side and gas side of packed valve to the open position 6 Mount the valve stem nuts a...
Страница 20: ...hesystem Thisisnecessaryforbetter vacuumoperation fullOPENpositionofElectronicExpansion Valve EEV WARNING Adding refrigerant If you install the excessive length of pipe add additional refrigerant as 10g 20g per unit meter refer to the table below Refer to the Service Manual for more details on this operation Model Total connecting pipe length L Adding refrigerant RJ040F2HX AJ040FCJ2 LTd15m Chargel...
Страница 21: ...o the inside of the stop valve cover Indoor unit Outdoor unit kg kg kg Contains fluorinated greenhouse gases covered by the Kyoto Protocol Note a Factoryrefrigerantchargeoftheproduct seeunitnameplate b Additionalrefrigerantamountchargedinthefield Refertotheaboveinformationforthequantityof refrigerantreplenishment c Totalrefrigerantcharge d Refrigerantcylinderandmanifoldforcharging Important inform...
Страница 22: ...wn the suction valves with the same wrench Turn the system off and switch mains supply off Disconnect pipes After disconnection protect valves and tubing ends from dust Compressor damage may occur if run at a negative suction pressure RJ060F3HX AJ068FCJ3 RJ070F4HX RJ080F4HX AJ070FCJ4 AJ080FCJ4 RJ040F2HX RJ050F2HX AJ040FCJ2 AJ050FCJ2 RJ052F3HX AJ052FCJ3 Follow different orders depending on the capa...
Страница 23: ...erant pipe A The outdoor unit is communication correctly together the indoor unit connected to refrigerant pipe B The outdoor unit is communication correctly together the indoor unit connected to refrigerant pipe C The outdoor unit is communication correctly together the indoor unit connected to refrigerant pipe D At this point it is possible to start the internal units in the desired mode 䭭 If do...
Страница 24: ...tion with indoor unit A 01 communication with indoor unit B 02 communication with indoor unit C 03 communication with indoor unit D IncaseofManualaddressmode youcandopipecheckoperationforcheckwhetheryouconnectthepipescorrectlyornot Butyouneedsetindooraddressswitchyourselves Switch Indoor unit address Display of the external unit Switch Indoor unit address Display of the external unit SW 02 Manual ...
Страница 25: ...C MH020FV N A MH023FB MH026FB V N A MH035FB V N A MH052FB V N A IT S HERE sw02 MAIN PCB SERIE VISION SLIM 1 WAY MH026FS MH035FS sw02 MINI 4 WAY MH030FM MH035FM MH052FM sw02 sw02 SLIM DUCT MSP DUCT MH026FE MH035FE NJ026LHX NJ035LHX MH052FU SW Same for CONSOLE MH026FJ MH035FJ MAIN PCB ...
Страница 26: ...n Push the K2 button three times Heat mode try run Push the K2 button once After 12 minutes of stationary condition check each indoor unit air treatment Cooling mode indoor unit check Inlet air temp Outlet air temp From 10 K to 12 K indicative deltaT Heating mode indoor unit check Outlet air temp Inlet air temp From 11 K to 14 K indicative deltaT In heating mode the indoor fan motor can remain off...
Страница 27: ...g on left side is increased by 1 and each time you press High Fan button 7 seg on right side is increased by 1 4 You press button to move to the next setteing page 5 After setting option press button to check whether the option code you input is correct or not 6 Press operation button with the direction of remote control for set t 4 4 4 4 BSF OPU TFU BT QBHF PQUJPO t 4FU UIF 4 4 BT 0 TUBUVT BOE 4 ...
Страница 28: ...on to enter SEG11 value 2 Press High Fan button to enter SEG12value Step 7 Press Mode button to be changed to AUTO mode in the OFF status 1 Press Fan button to enter SEG14 value 2 Press High Fan button to enter SEG15 value Step 8 Press Mode button to be changed to Cool mode in the OFF status 1 Press Low Fan button to enter SEG16 value 2 Press High Fan button to enter SEG17 value Step 9 Press Mode ...
Страница 29: ...4 SEG5 SEG6 Explanation PAGE MODE Setting Main address 100 digit of indoor unit address 10 digit of indoor unit A single digit of indoor unit Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A single digit 1 Main address setting mode ...
Страница 30: ...ails Indication Details Indication Details Indication Details Indication Details 1 0 0 0 0 0 Slave 1 Master Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation PAGE External control External control output Buzzer Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 2 0 No use 0 Thermo ON 0 0 Use 0 1 On Off contr...
Страница 31: ... the outdoor temperature is below 5 C Do not adjust the Ampere Limit Switch if it s not necessary before modifying it evaluate the total number of electric and electronics loads consumption and use Ampere limits switch just as emergency solution or in case the system is anyway oversized compared to real thermal load needed Ampere Limit Switch is initially set to the default value table below Amper...
Страница 32: ...ge temperature 1 Target Compressor Frequency 9 OLP temperature 2 Order Compressor Frequency 10 Condenser temperature 3 EEV0 current step 11 Outdoor temperature 4 EEV1 current step 12 Running current 5 EEV2 current step 13 Target Discharge temperature 6 EEV3 current step3 14 Total capacity of the indoor units 7 Fan RPM H high L low Blank off 15 Safety Control just For ServiceTechnician TheEEV2andEE...
Страница 33: ...k occasion trytooperationaftertheinstallationthroughautoaddressingmodewithoutpipecheckoperation Check setting The number of Indoor unit mismatched Check electrical connection and setting Communication error between the outdoor and indoor unit Check electrical connection and setting Outdoor communication error between main micom and inverter micom Outdoor communication error beween main micom and h...
Страница 34: ...unit EEV open operating indoor unit s Self diagnosis High temperature over 30 C of outdoor as heating mode Low temperature under 10 C of outdoor as cooling mode Outdoor Fan Error Communication cable mismatched between indoor and outdoor unit Check electrical connection Inverter compressor starting failure 5 times Compressor trip by input current control mode PFC over current Compressor trip by OLP...
Страница 35: ...pages in the owner s instruction booklet 1 How to start and stop the air conditioner 2 How to select the operating mode and adjust the temperature and fan settings 3 How to adjust the air flow direction 4 How to set the timers 5 How to remove and clean the filters 1 Turn on the air conditioner and select Cool mode or pump down mode to run the compressor for 3 minutes 2 Release the valve caps on Hi...
Страница 36: ... EEE Yönetmeliğine Uygundur This EEE is compliant with RoHS ...
Страница 37: ...chasing this Samsung product To receive more complete service please register your product at www samsung com register DB98 33017A 5 EN RJ040F2HX77 RJ050F2HX77 RJ052F3HX77 RJ060F3HX77 RJ070F4HX77 RJ080F4HX77 AJ777FCJ777 This manual is made with 100 recycled paper ES FR IT PT DE EL ...