13
English
Installation Pr
oc
edur
e
5
Push the drain hose up to insulation when connecting
the drain hose to drain socket.
Metal clamp
Drain socket
Drain hose
Large seailng pad
Drain pipe
Be sure to bond the
drain hose and the
main pipe.
Drain hose
PVC Tube Joint
+ VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
• Install air ventilation to drain condensation smoothly.
Ceiling
Air ventilation
• If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than 550
mm, there may be water leaks.
Band joint
300 mm
or less 20 mm or more
Ceiling
1/100 or more
300
to
550 mm
Drain hose
• Do not give the hose an upward gradient beyond
the connection port. This will cause water to flow
backwards when the unit is stopped, resulting in water
leaks.
Ceiling
Under gradient
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
Ceiling
Support pieces
1 to 1.5 m
1/100 or more
• Install
horizontally.
Indoor unit
Be horizontal
Flexible hose
• Max. allowable aixs gap
Max. 20 mm
Indoor unit