MAINTENANCE
65
English
Item
Chilled water system
Heating water system
Effect
Low level medium temperature
heating gauge
Circulation water
(Below 20°C
(68°F))
Supply water
Circulation water
(Over 20°C (68°F)
below 60°C (140°F))
Supply water Corrosion
Forming
scale
Basic item
Acid consumption
(pH4.8, mgCaCO
3
/l)
Below 50
Below 50
Below 50
Below 50
O
Full hardness
(mgCaCO
3
/l)
Below 70
Below 70
Below 70
Below 70
O
Calcium hardness
(mgCaCO
3
/l)
Below 50
Below 50
Below 50
Below 50
O
Ion-like silica (mgSiO
2
/
l)
Below 30
Below 30
Below 30
Below 30
O
Reference
item
Iron (mgFe/l)
Below 1.0
Below 0.3
Below 1.0
Below 0.3
O
Copper (mgCu/l)
Below 1.0
Below 0.1
Below 1.0
Below 0.1
O
Sulfide ion (mgS
2-
/l)
Not detected
Not detected
Not detected
Not detected
O
Ammonium ion
(mgNH
4
+
/l)
Below 1.0
Below 0.1
Below 0.3
Below 0.1
O
Chlorine residual
(mgCl/l)
Below 0.3
Below 0.3
Below 0.25
Below 0.3
O
Free carbon (mgCO
2
/l)
Below 4.0
Below 4.0
Below 0.4
Below 4.0
O
NOTE
ŷ
Circle (O) marks in the chart show the factor relevant to corrosion or water scale.
ŷ
When the water temperature is over 40°C (104°F), steels without protective coating may corrode when expose
to water. Applying corrosion prevention material or degassing can be effective measure to prevent corrosion.
ŷ
Circulating water and supply water should satisfy the standard shown in the table.
ŷ
Supplied water or make-up water should be supplied by purified water, neutralized water, tap water except
softened water, and industrial water.
ŷ
14 items in the table is a typical factor for corrosion and/or water scale.
Содержание AG010KSV Series
Страница 85: ...MAINTENANCE 85 English MEMO ...
Страница 86: ......