Troubleshooting
50
Samsung Electronics
Yes
Is EEV wire normal?
(Normal: The wire between EEV
and blue-6pin-connector is not cut)
Remove EEV connector from the PBA CN81.
Check Each resistance.
[red-brn : 0ohm /
red-(wht,yel,org,blu) : over 20~1kohm]
Check EEV wire.
Yes
No
Restore wire
pin#1;wht, pin#2;yel, pin#3;org,
pin#4;blu, pin#5;red, pin#6;brn
Does the each resistance
lie in its range?
Yes
No
Replace the EEV.
Is each sensor at the right position?
Yes
No
Move each sensor to its right position.
Are the pipes damaged or blocked up
in the OUTDOOR UNIT?
Yes
No
Repair the pipes and recharge
the refrigerant.
Change the MAIN PCB
4-2-5 EEV error (E419)
1. Check items
1) Does the compressor rotate normally?
2) Is the OLP sensor normal?
2. Check procedure