33
ENGLISH
Power Cable Specifications
1 phase
Outdoor unit
Rated
Voltage Range
MCA
MFA
Hz
Volts
Min
Max
Min. Circuit Amps.
Max. Fuse Amps.
AE080RXYDEG
50
220-240
198
264
22 A
27.5 A
AE120RXYDEG
50
220-240
198
264
28 A
35 A
AE160RXYDEG
50
220-240
198
264
32 A
40 A
f
The power cable is not supplied with Air to water heat pump.
f
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
f
This Equipment complies with IEC 61000-3-12.
Indoor Unit
Load
Power supply
Power cable
MAX. length
Type GL
mm
2
,wires
m
A
MIM-E03CN
No Heater
(Water Pump, Valve, Wired RMC)
1Ø, 220-240V,
50Hz
1.5 / 3
<10m
10
2.5 / 3
10m<L<20m
10
Booster Heater (3kw)
4.0 / 3
<10m
20
6.0 / 3
10m<L<20m
20
Booster Heater (~3kw)
+ Backup Heater (~3kw)
6.0 / 3
<10m
40
8.0 / 3
10m<L<20m
40
f
The Power cable is not supplied with the heat pump.
f
For power cable, use the grade H05RN-F materials in 1Ø system.
f
If you connect Backup Heater at separated power cable, you can reduce wire size. (Please refer to control kit installation
manual)
3 Phase
Outdoor unit
Rated
Voltage Range
MCA
MFA
Hz
Volts
Min
Max
Min. Circuit Amps.
Max. Fuse Amps.
AE080RXYDGG
50
380-415
342
457
10 A
16.1 A
AE120RXYDGG
50
380-415
342
457
10 A
16.1 A
AE160RXYDGG
50
380-415
342
457
12 A
16.1 A
f
The power cable is not supplied with air to water heat pump.
f
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
f
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
3.3[MVA] at the interface point between the user's supply and the public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 3.3[MVA].