14
Installation Procedure
English
Instal
lation Pr
oc
edur
e
When the installation template is made of plastic
1 way Cassette
Unit : inch(mm)
1 way Cassette (WindFree panel)
①
WindFree medium/
large type (outlet)
①
WindFree medium/
large type (inlet)
Indoor unit
Clamping jig
0.39(10)
0.39(10)
When the installation template is made of paper
1 way Cassette
Unit: inch(mm)
1way cassette (WindFree panel)
(AC009BN1DCH, AC012BN1DCH)
1way cassette (WindFree panel)
(AC018BN1DCH)
1way cassette (General panel)
(AC009BN1DCH, AC012BN1DCH)
1way cassette (General panel)
(AC018BN1DCH)
Indoor unit
Air outlet side
Jig
Jig
0.
39(
10)
0.
39(
10)
0.
39(
10)
0.
39(
10)
0.
59(
15)
0.
59(
15)
0.
59(
15)
0.
59(
15)
Ceiling
Ceiling
Ceiling
Ceiling
Jig
Jig
Air outlet side
Air outlet side
Air outlet side
Air inlet side
Air inlet side
Air inlet side
Air inlet side
Indoor unit
Indoor unit
Indoor unit
4 way Cassette
Indoor unit
Ceiling
Gauge of dimensions
0.67 inch (17 mm)
0.79 inch (20 mm)
Step 5 Purging inert gas from the
indoor unit
The indoor unit comes with nitrogen gas (inert gas)
charged at the factory. Therefore, all inert gas must be
purged before connecting the refrigerant pipes.
Unscrew the pinch pipe at the end of each refrigerant pipe.
1 way Cassette
Liquid side
Gas side
Insulator
4 way Cassette
Liquid side
Gas side
Insulator
NOTE
• To prevent dirt or foreign objects from getting into the
pipes during installation, do not remove the pinch pipe
completely until you are ready to connect the piping.
Step 6 Cutting and flaring the pipes
1
Make sure that you have the required tools available:
pipe cutter, reamer, flaring tool, and pipe holder.
2
If you wish to shorten the pipes, cut them with a pipe
cutter, ensuring that the cut edge remains at a 90° angle
to the side of the pipe. Refer to the illustrations below
for examples of edges cut correctly and incorrectly.