Samsung Electronics
4-9
•
Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3 minute delay).
•
If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
•
If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set to 0
(Indoor 1).
•
Default value of Heating setting compensation (SEG21) is 5°C for 360 cassette model.
* Level control: The centralized controller can limit the functions and inputs of connected products with this function
enabled. (Example: Operation mode limit (Cooling only/Heating only/No limitation), Heating
temperature upper limit, Cooling temperature lower limit)
To enable 'Level control' when applying the DPM with the centralized controller, appoint the master (Set
'Use of external control [SEG14] option to 4 or higher).
Example: When installing DPM (1 Outdoor unit with 4 indoor units)
Condition
SEG14 Setting
Result
External control
Level control
Indoor 1
Indoor 2
Indoor 3
Indoor 4
Default
Not set (0)
Slave (All)
Disuse
Use
4
Not set (0)
Not set (0)
Not set (0)
Master (Indoor 1), Slave
(Indoor 2,3,4)
Use (Indoor 3)
Disuse
Not set (0)
Not set (0)
1~3
Not set (0)
Slave (All)
Use (Indoor 4)
Use
Not set (0)
Not set (0)
Not set (0)
5~7
Master (Indoor 4), Slave
(Indoor 1,2,3)
4-1-4 Changing the addresses and options individually
When you want to change the value of a specific option, refer to the following table and follow the steps in
Common
steps for setting the addresses and options
on page
<?>
.
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Option mode to
change
Tens position
of the option
number
Units position
of the option
number
New value
Indication
and details
Indication Details Indication Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
D
Option
type
0 to F
Tens
position
value
0 to 9
Units
position
value
0 to 9
New
value
0 to F
Example: Changing the Buzzer control (SEG17) option of the installation options to 1 disuse.
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Option mode to
change
Tens position
of the option
number
Units position
of the option
number
New value
Indication
0
D
2
1
7
1
Содержание AC035MNADKH/EU
Страница 15: ...3 6 Samsung Electronics No Parts Procedure Remark 9 RemovethePanelFrame fromtheMain Frameasshownontherightside ...
Страница 81: ...Samsung Electronics 5 5 5 2 2 MAIN PCB AC052MXADKH 5 4 3 2 1 7 6 8 9 10 11 12 ...
Страница 87: ...Samsung Electronics 6 3 AC052MXADKH AC071MXADKH This Document can not be used without Samsung s authorization ...