Samsung Electronics
4-3
4-2 Outdoor Trouble shooting
◆
If an error occurs during the operation, it is displayed on the outdoor unit PCB.
No.
Meaning
Remarks
Error Code
1
Unit quantity miss matching between indoor and outdoor.
Check indoor quantity setting in outdoor
E201
2
Abnormal state, no communication between Indoor and Outdoor
Main PCB
Check electrical connection and setting
E202
3
1min. Time out of communcation error(Main
Ê
Inverter)
Check electrical connection and setting
E203
4
Outdoor temp sensor error
Check Outdoor sensor Open/Short
E221
5
Cond. temp sensor error
Check Cond. sensor Open/Short
E231
6
Discharge temp sensor error
Check Discharge sensor Open/Short
E251
7
OLP Sensor Error
Check OLP sensor Open/Short
E320
8
Detection of Outdoor Freezing when Comp. Stop
Check Outdoor Cond.
E403
9
Protection of Outdoor Overload when Comp. Stop
Check Comp. when it start
E404
10
Discharge temperature of a compressor in an
outdoor unit is overheated.
E416
11
Heating operation is not available since the outdoor air tem-
perature is over 30°C.
Heating
E440
Cooling operation is not available since the outdoor air tem-
perature is lower than -5°C.
Cooling
E441
12
Outdoor unit BLDC Fan 1 or Fan 2 error
FAN1 error
E458
FAN2 error
E475
13 Comp. Starting error
E461
14 Primary Current Trip error
E462
15 Over current trip / PFC over current error
Check OLP sensor
E463
16 IPM(IGBT Module) Over Current(O.C)
E464
17 Comp. Over load error
E465
18 DC-Link voltage under/over error
Check AC Power or DC_Link voltage
E466
19 Comp. wire missing error
Check Comp. wire
E467
20 Current sensor error
Check Outdoor Inverter PBA
E468
21 Outdoor EEPROM error
Check Outdoor EEPROM data
E471
22 IPM(IGBT Module) or PFCM Temperature sensor Error
Check Outdoor Inverter PBA
E474
23 PFC Overload Error
Check Outdoor Inverter PBA
E484
24 IPM is over heated.
Check Outdoor Inverter PBA
E500
25 GAS Leak error
Check indoor and outdoor unit model
E554
26 Capacity miss match between indoor and outdoor
Check indoor and outdoor unit model
E556
27 Option code miss matching among the indoors (only for DPM)
Check indoor option code
E557
28 Outdoor EEPROM error (checksum)
Check Outdoor EEPROM data
E470
29
EEV or Valve Close error-Self diagnosis
1. Check if the service valve is open
2. Check for refrigerant leakage (pipe connections, heat
exchanger) and charge refrigerant if necessary
3. Check if there's any blockage on refrigerant cycle
(indoor unit/outdoor unit)
4. Check if additional refrigerant has been added after
pipe extension
E422
30
Outdoor EEPROM checksum error between MAIN and INVERTER. Check Outdoor Inverter PBA
E590
|
Off
Blink
z