4-20
Samsung Electronics
Yes
No
No
In this case, is the resistance
value out of range in the temperature table
on the right?
Yes
Is the indoor heat exchanger
temperature sensor connector disconnected
from the PCB?
Restart the system after replacing the PCB
Restart the system after
connecting the connector to PCB
Failure of the indoor heat
exchanger temperature sensor
(replace)
Remove the indoor heat exchanger
temperature sensor connector from
the PCB and measure the resistance
between two terminals
Indoor unit display
4way
(Operation)
(Defrost) X (Timer) X (Filter)
1way
(Operation)
X (Defrost)
(Reservation)
X
(Fan) X (Filter)
Symptom
Short or open circuit of indoor heat exchanger temperature sensor
Failure
Short or open circuit in the corresponding sensor
4-3-2 Indoor heat exchanger temperature sensor (open/short)
Current
temperature
(°C)
Resistance
(kΩ)
40
5.800
35
6.900
30
8.300
25
10.00
20
12.10
15
14.70
10
18.00
5
22.00
0
28.30
-5
33.90
-10
42.30
<Temperature sensor