3 . Press K1 or K2 on the outdoor unit PCB to run the test mode and stop .
K1
Mode
DISPLAY
1
Heating Test Mode
2
Defrost Test Mode
K2
Mode
DISPLAY
1
Cooling Test Mode
2
Inverter checker
(Load PBA inspection operation)
3
Pump down in Cool mode
Condition 1 : The outdoor temperature is under 50 °F
Condition 2 : All the temperature conditions should meet the defrost conditions
4 . After 12 minutes of stationary condition check each indoor unit air treatment :
f
f
Cooling mode(indoor unit check)
Inlet air temp . – Outlet air temp . ≥ 18 °F(reference only)
f
f
Heating mode(indoor unit check)
Inlet air temp . – Outlet air temp . ≥ 19 .8 °F(reference only)
f
f
In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space .
5 . How to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode) :
f
f
Press [K3] button over 1 sec to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode) .
6 . View Mode : When the K4 switch is pressed, you can see information about our system state as below .
Short
push
Display contents
SEG1
SEG2
SEG3
SEG4
Unit
1
Order frequency
1
Hundreds' digit Tens' digit
Unit digit
Hz
2
Current frequency
2
Hundreds' digit Tens' digit
Unit digit
Hz
3
The number of current indoor units
3
Hundreds' digit Tens' digit
Unit digit
EA
4
The sensor for outdoor air intake
4
+ / -
Tens' digit
Unit digit
°C
5
Discharge sensor
5
Hundreds' digit Tens' digit
Unit digit
°C
6
Eva-Mid sensor
6
+ / -
Tens' digit
Unit digit
°C
7
Cond sensor
7
+ / -
Tens' digit
Unit digit
°C
8
Current
8
Tens' digit
Unit digit
The first place of
decimals
A
9
Fan RPM
9
Thousands'
digit
Hundreds' digit
Tens' digit
rpm
10
Target discharge temperature
A
Hundreds' digit Tens' digit
Unit digit
°C
11
EEV
B
Hundreds' digit Tens' digit
Unit digit
step
12
The capacity sum of indoor units
C
Tens' digit
Unit digit
The first place of
decimals
kW
13
Protective control
D
0: Cooling
1: Heating
Protective control
0: No Protective control
1: Freezing
2: Non-stop defrosting
3: Over-load
4: Discharge
5: Total electric current
Frequency status
0: Normal
1: Hold
2: Down
3: Up_limit
4: Down_limit
-
14
The temperature of heat radiating
plate
E
Hundreds' digit Tens' digit
Unit digit
-
15
S/W check
F
-
-
-
-
29
ENGLISH
4way Outdoor_북미향_IM_EN_DB68-05152A-00_CS6.indd 29
2015-01-05 오후 5:00:50