Troubleshooting
4-16
Samsung Electronics
4-2-4 Outdoor Unit
No. Error Code
Meaning
Remarks
1
E108
Error due to duplicated communication address Check on repeated indoor unit main address
2
E121
Error on room temperature sensor of indoor unit
(Short or Open)
Indoor unit Room Thermistor Open/Short
3
E122
Error on EVA IN sensor of indoor unit (Short or Open) Indoor unit EVA_IN Thermistor Open/Short
4
E123
Error on EVA OUT sensor of indoor unit (Short or Open) Indoor unit EVA_OUT Thermistor Open/Short
5
E153
Error on float switch (2nd detection)
Indoor unit Float Switch Open/Short Drain
Pump operation Check
6
E154
Indoor fan error
Check on indoor unit indoor Fan operation
7
E164
Error due to connecting outdoor units that do
not support the Wind-Free function
Check outdoor main PBA S/W, Check
outdoor EEPROM data
8
E201
Communication error between the indoor unit
and outdoor unit (Pre-tracking failure or when
the actual number of indoor units are different
from the indoor unit quantity setting on the
outdoor unit) Error due to communication
tracking failure after initial power is supplied (The
error occurs regardless of the number of units.)
Check indoor quantity setting in outdoor
9
E202
Communication error between indoor unit and
outdoor unit (When there is no response from
indoor units after tracking is completed)
Check electrical connection and setting
between indoor unit and outdoor unit
10
E203
Communication error between the outdoor unit
and main micom (For PF #4 to #6 controllers,
error will be determined from the time when
the compressor is turned on.)
Check electrical connection and setting
between
outdoor unit MAIN PBA - INVERTER PBA
11
E221
Error on outdoor temperature sensor (Short or
Open)
Check Outdoor sensor Open / Short
12
E231
Error on outdoor COND OUT sensor (Short or Open) Check Cond-Out sensor Open / Short
13
E251
Error on discharge temperature sensor of
compressor 1 (Short or Open)
Check Discharge sensor Open / Short
14
E320
Error on OLP sensor (Short or Open)
Check OLP sensor Open / Short
15
E403
Compressor down due to freeze protection control Check Outdoor Cond.
16
E404
System stop due to overload protection control Check Comp. when it starts
17
E407
High Pressure Switch Error or High Pressure
Switch Connector Open
Check Comp Pressure or Check the Connection
of the CN003 on the MAIN-OUT PBA
(Error that only covers an outdoor unit capacity
of 7.1 KW or less)
18
E416
System stop due to discharge temperature
-
19
E422
Blockage detected on high pressure pipe
1. Check if the service valve is open
2. Check for refrigerant leakage (pipe
connections, heat exchanger) and charge
refrigerant if necessary
3. Check if there's any blockage on the
refrigerant cycle (indoor unit/outdoor unit)
4. Check if Additional refrigerant has been
added after pipe extension
Содержание AC026RN1DKG
Страница 215: ...PCB Diagram and Parts List Samsung Electronics 5 7 AC026 035 052 071RNLDKG 1 2 15 5 4 10 9 6 7 8 11 12 15 16 13 14 ...
Страница 219: ...PCB Diagram and Parts List Samsung Electronics 5 11 AC026 035 052RNJDKG ...
Страница 221: ...PCB Diagram and Parts List Samsung Electronics 5 13 AC100 120 140RNCDKG 1 2 3 4 5 6 7 8 9 10 11 12 13 14 18 15 16 17 19 ...
Страница 228: ...PCB Diagram and Parts List 5 20 Samsung Electronics 1 2 3 4 5 6 7 8 9 11 10 12 12 13 AC100 120 140RXAD G ...
Страница 247: ...Wiring Diagram Samsung Electronics 6 9 Indoor Unit cont AC026 035 052RNJDKG ...
Страница 248: ...Wiring Diagram 6 10 Samsung Electronics Indoor Unit cont AC100 120 140RNCDKG ...
Страница 251: ...Wiring Diagram Samsung Electronics 6 13 Outdoor unit cont AC100 120 140RXADKG EU ...
Страница 252: ...Wiring Diagram 6 14 Samsung Electronics Outdoor unit cont AC100 120 140RXADNG EU ...