With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition.
If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that
the duct becomes shorter, adjust the fan speed by referring the following table.
E. S. P(External Static Pressure) setting for phase control motor
• If the coil is not dry, run the unit for 2 hours with fan only to dry the coil.
•
The air filter is properly attached into the air passage on the air suction side of the air conditioning unit.
• Adjust the dampers so that each air inlet and outlet exhusts the designed airflow rate.
• If using booster fans(an outdoor air processing unit or ERV via duct), do not use Automatic Air-Volume function.
• If the duct configurations have been changed, automatic air-volume function perform again.
• The product can be used within the range of rated voltage 220 V/230 V/240 V ± 5 V. If the product needs to be
installed in the condition that is out of the rated voltage stated above, additional setting with installation option is
required.
Model
AC035HBMDKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤2.5
01B06C-1C5084-272328-374000
2.5< SP ≤5
01B06C-1C50EB-272328-374000
5< SP ≤7.5
01B06C-1C5552-272328-374000
7.5< SP ≤10
01B06C-1C55CA-272328-374000
10< SP ≤12.5
01B06C-1C5A30-272328-374000
12.5< SP ≤15
01B06C-1C5A85-272328-374000
Model
AC120HBMPKH
AC140HBMPKH
AC140HBMDKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤5.2
01B06C-1C542C-
27788C-372045
01B06C-1C544C-
278CA0-371045
01B06C-1C544C-
278CA0-371045
5.2< SP ≤8
01B06C-1C5572-
27788C-372045
01B06C-1C5592-
278CA0-371045
01B06C-1C5592-
278CA0-371045
8< SP ≤12
01B06C-1C55EA-
27788C-372045
01B06C-1C55FA-
278CA0-371045
01B06C-1C55FA-
278CA0-371045
12< SP ≤ 15
01B06C-1C592E-
27788C-372045
01B06C-1C593E-
278CA0-371045
01B06C-1C593E-
278CA0-371045
Model
AC090HBMDKH
AC100HBMDKH
AC090HBMPKH
AC100HBMPKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤4
01B06C-1C546F-
275A64-372020
01B06C-1C549F-
276470-371020
01B06C-1C50B7-
275A64-374040
01B06C-1C50F9-
276470-373040
4< SP ≤8
01B06C-1C55E8-
275A64-372020
01B06C-1C5928-
276470-371020
01B06C-1C543F-
275A64-374040
01B06C-1C5540-
276470-373040
8< SP ≤12
01B06C-1C5A61-
275A64-372020
01B06C-1C5AB1-
276470-371020
01B06C-1C55A7-
275A64-374040
01B06C-1C55B9-
276470-373040
12< SP ≤15
01B06C-1C5AC8-
275A64-372020
01B06C-1C5AE8-
276470-371020
01B06C-1C55FD-
275A64-374040
01B06C-1C591F-
276470-373040
Model
AC052HBLDKH
AC071HBLDKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤3
01C06C-1C5925-27343C-370000
01C06C-1C59E8-274750-370000
3< SP ≤4
01C06C-1C596B-27343C-370000
01C06C-1C5D2D-274750-370000