Samsung Electronics
4-9
4-2-2 Troubleshooting for outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
No.
Error Code
Meaning
Remarks
1
E201
Unit quantity miss matching between indoor and outdoor.
Check indoor quantity setting in outdoor
(Refer to page 17.)
2
E202
Abnormal state, no communication between Indoor and Outdoor
Main PCB
Check electrical connection and setting
3
E203
1min. Time out of communcation error(Main
Inverter)
Check electrical connection and setting
4
E221
Outdoor temp sensor error
Check Outdoor sensor Open/Short
5
E231
Cond. temp sensor error
Check Cond. sensor Open/Short
6
E251
Discharge temp sensor error
Check Discharge sensor Open/Short
7
E320
OLP Sensor Error
Check OLP sensor Open/Short
8
E403
Detection of Outdoor Freezing when Comp. Stop
Check Outdoor Cond.
9
E404
Protection of Outdoor Overload when Comp. Stop
Check Comp. when it start
10
E416
Discharge temperature of a compressor in an
outdoor unit is overheated.
11
E440
Heating operation is not available since the outdoor air tempera-
ture is over 30°C.
Heating
E441
Cooling operation is not available since the outdoor air tempera-
ture is lower than -5°C.
Cooling
12
E458
Outdoor unit BLDC Fan 1 or Fan 2 error
FAN1 error
E475
FAN2 error
13
E461
Comp. Starting error
14
E462
Primary Current Trip error
15
E463
Over current trip / PFC over current error
Check OLP sensor
16
E464
IPM(IGBT Module) Over Current(O.C)
17
E465
Comp. Over load error
18
E466
DC-Link voltage under/over error
Check AC Power or DC_Link voltage
19
E467
Comp. wire missing error
Check Comp. wire
20
E468
Current sensor error
Check Outdoor Inverter PBA
21
E471
Outdoor EEPROM error
Check Outdoor EEPROM date
22
E474
IPM(IGBT Module) or PFCM Temperature sensor Error
Check Outdoor Inverter PBA
23
E484
PFC Overload Error
Check Outdoor Inverter PBA
24
E500
IPM is over heated.
Check Outdoor Inverter PBA
25
E554
GAS Leak error
Check indoor and outdoor unit model
26
E556
Capacity miss match between indoor and outdoor
Check indoor and outdoor unit model
Содержание AC026FBRDEH
Страница 10: ...Samsung Electronics 3 1 Necessary Tools Item Remark SCREW DRIVER MONKEY SPANNER 3 Disassembly and Reassembly...
Страница 19: ...3 10 Samsung Electronics No Parts Procedure Remark 6 Loosen fixing screws of the Cabinet Front...
Страница 58: ...Samsung Electronics 5 1 5 PCB Diagram and Parts List 5 1 PCB Diagram 5 1 1 Indoor Unit...
Страница 63: ...Samsung Electronics 6 1 6 Wiring Diagram 6 1 Indoor Unit...
Страница 64: ...Samsung Electronics 6 2 6 2 Outdoor Unit...