10
Installation Procedure
Ins
tallation Pr
oc
edur
e
English
7
Adjust the unit to the appropriate position, taking into
account the installation area for the front panel.
•
Place the pattern sheet on the indoor unit.
•
Adjust the space between the ceiling and the
indoor unit by using a dimension gauge.
•
Fix the indoor unit securely after adjusting the
level of the unit by using a leveller.
•
Remove the pattern sheet and install the front
panel.
For the recessed installation
of the square panel:
11.5 mm (0.45 in.)
For the recessed installation
of the circular panel:
41.5 mm (1.63 in.)
Indoor unit
Ceiling
Gauge of
dimensions
Step 5 Purging inert gas from the
indoor unit
The indoor unit comes with nitrogen gas (inert gas)
charged at the factory. Therefore, all inert gas must be
purged before connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant
pipe.
Liquid side
Gas side
Insulator
NOTE
•
To prevent dirt or foreign objects from getting into
the pipes during installation, do not remove the pinch
pipe completely until you are ready to connect the
piping.
Step 6 Cutting and flaring the pipes
1
Make sure that you have the required tools available:
pipe cutter, reamer, flaring tool, and pipe holder.
2
If you wish to shorten the pipes, cut them with a pipe
cutter, ensuring that the cut edge remains at a 90°
angle to the side of the pipe. Refer to the illustrations
below for examples of edges cut correctly and
incorrectly.
Pipe cutter
Pipe
Oblique
Rough
Burr
3
To prevent any gas from leaking out, remove all burrs
at the cut edge of the pipe, using a reamer.
4
Slide a flare nut on to the pipe and modify the flare.
Pipe
Flare
D
A
Flare
R 0.4 to 0.8 mm
(0.016 to 0.032 in.)
D
L
90° ±2°
45
°
±2
°
Outer Diameter (D)
Depth (A)
Flare dimension (L)
mm
inch
mm
inch
mm
inch
6.34
1/4
1.3
0.051
8.7 to 9.1
0.34 to 0.36
9.52
3/8
1.8
0.071 12.8 to 13.2
0.5 to 0.52
12.7
1/2
2.0
0.079 16.2 to 16.6 0.64 to 0.65
15.88
5/8
2.2
0.087 19.3 to 19.7 0.76 to 0.78
19.05
3/4
2.2
0.087 23.6 to 24.0 0.93 to 0.95