Troubleshooting
4-14
Samsung Electronics
Option
SEG19
SEG20
SEG21
SEG22
SEG23
7)
SEG24
Function
Page
Individual control with
remote control
5)
Heating setting
compensation
6)
Reserved
Setting the MDS Kit installation option
Reserved
Indication
and
details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
3
0 or 1
Indoor1
0
Default
0
Disuse (Soft Off+Hard off)
2
Indoor2
1
3.6˚F(2˚C)
Standard
1
Off after 20 min.
(Soft Off+Hard off)
3
Indoor3
2
9˚F(5˚C)
2
Off after 40 min.
(Soft Off+Hard off)
4
Indoor4
3
Off after 80 min.
(Soft Off+Hard off)
Premium
4
Off after 20 min.
(Soft Off+Hard off)
5
Off after 40 min.
(Soft Off+Hard off)
6
Off after 80 min.
(Soft Off+Hard off)
Standard
7
Off after 20 min.
(Soft Off only)
8
Off after 40 min.
(Soft Off only)
9
Off after 80 min.
(Soft Off only)
Premium
A
Off after 20 min.
(Soft Off only)
B
Off after 40 min.
(Soft Off only)
C
Off after 80 min.
(Soft Off only)
• 1) SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
– Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
– Fan stops or operates Ultra low in Cooling when thermostat is off.
• 2) SEG8
Even if you set the Use of drain pump option to 0, it is utomatically set to 2 (the drain pump is used with 3 minute delay).
• 3) SEG11
Compensation of the WindFree fan RPM option adjusts 20 rpm per 1 step.
• 4) SEG18
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
• 5) SEG20
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1)
• 6) SEG21
Default value of Heating setting compensation is 9°F(5℃).
• 7) SEG23
Soft Off
: The indoor unit turns off its operation at the indicated time in the table for Installation Option after its final motion detection. But, it turns on
again if the MDS detects motion.
Hard Off
: Designated time after SOFT OFF, it cannot turn on automatically when it detects motion. Users should control to turn on the indoor unit with
remote control, etc.
Содержание AC009BNLDCH
Страница 187: ...Disassembly and Reassembly 3 134 Samsung Electronics No Parts Procedure Remark 7 Cabinet Front LF ...
Страница 291: ...PCB Diagram and Parts List Samsung Electronics 5 13 RAC AC018 024BNADCH 1 2 3 11 4 5 12 7 6 10 9 8 ...
Страница 293: ...PCB Diagram and Parts List Samsung Electronics 5 15 RAC AC030 036BNTDCH ...
Страница 305: ...PCB Diagram and Parts List Samsung Electronics 5 27 5 4 Outdoor Unit Main PBA PF2 3 AC009 012 018BXADCH AC018 024BXSCCC ...
Страница 307: ...PCB Diagram and Parts List Samsung Electronics 5 29 PF4 5 AC024 030 036 042 048BXADCH AC030 036BXSCCC AC030 036BXSCCH ...