Step 14 Optional: Extending the
power cable
1
Prepare the following tools.
Tools
Spec
Shape
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)
2
As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
ŷ
Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
ŷ
For information about the power cable
specifications for indoor and outdoor units, refer
to the installation manual.
ŷ
After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
Power cable
Pre-installed tube for the power cable
(Unit: mm)
(Unit: mm)
20
20
20
20
60
120
180
3
Insert both sides of core wire of the power cable into
the connection sleeve.
ŷ
Method 1
: Push the core wire into the sleeve from
both sides.
ŷ
Method 2
: Twist the wire cores together and push
it into the sleeve.
Connection sleeve
Connection sleeve
Method 1
Method 2
4
Using a crimping tool, compress the two points and
flip it over and compress another two points in the
same location.
ŷ
The compression dimension should be 8.0.
Compression
dimension
ŷ
After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Compress it 4 times.
5 mm
Compress it 4 times.
5 mm
Method 1
Method 2
5
Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
Three or more layers of insulation are required.
Method 1
Method 2
Insulation tape
35 mm
40 mm
Insulation tape
Содержание AC RN DKG Series