17
ENGLISH
Wiring diagram
1(L) 2(N)
Indoor Unit
Outdoor Unit
Indoor Power
Main power cable
Cable clmap
Cable clmap
Communication cable
V1
V2
F3
F4
1(L) 2(N)
N
L
F2
F1
F2
F1
Between Indoor and Outdoor Connection cable Specifications(Common in use)
Indoor Power supply
Communication Cable
Power Supply
Max/Min(V)
Indoor Power cabel
208~230V/60Hz
±10%
0.0039in²
Ĺ
,3wires
(2.5mm²
Ĺ
,3wires)
16/2 AWG shielded cable
(0.75~1.25mm²,2wires)
t
Selecting wire size must comply with local and national code.
t
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code
designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
t 4DSFXTPOUFSNJOBMCMPDLNVTUOPUCFVOTDSFXFEXJUIUIFUPSRVFMFTTUIBOLHGtDN
t
Since it has the external power supply, refer to the outdoor unit installation manual for MAIN POWER.
Terminal Block SPEC (Indoor)
AC POWER : M4 SCREW
COMMUNICATION : M4 SCREW
0.43(8.4)
0.51(9.5)
0.43(8.4)
0.51(9.5)
0.7(10.0)
0.7(10.0)
Tightening Torque
M4
12.0~18.0 (kgf·cm)
0.86~1.3.0 (lbf·ft)
WARNING
In case of extending the electric wire, please
DO NOT use a round-shaped pressing socket.
- Incomplete wire connections can cause
electric shock or a fire.