38
t
represents E. S. P(External Static Pressure) range of factory setting.
You don’t have to adjust the fan speed separately if the external static pressure of the installation place is in
. When it is out of
, input the appropriate option code.
t
If you input the inappropriate option code, error may occur or the air conditioner is out of order. The
option code must be inputted correctly by the installation specialist or service agent.
Adjusting air flow
Model
AC024MNHDCH
Static Pressure(mmAq)
Option code for indoor unit
SP= 2.5
01B0EC-1E5407-274750-374020
2.5<SP≤ 6
01B0EC-1E547B-274750-374020
6<SP≤ 9
01B0EC-1E55D1-274750-374020
9 <SP≤ 12
01B0EC-1E5937-274750-374020
12<SP≤ 15
01B0EC-1E599D-274750-374020
15<SP≤ 17.5
01B0EC-1E5AF3-274750-374020
17.5<SP≤ 20
01B0EC-1E5E59-274750-374020
Model
AC030MNHDCH
AC036MNHDCH
AC042MNHDCH
Static Pressure(mmAq)
Option code for indoor unit
3≤SP≤4
01B0EC-1E54B8-
275A64-376020
01B0EC-1E5403-
276470-376045
01B0EC-1E5424-
277D8C-377045
4<SP≤8
01B0EC-1E5920-
275A64-376020
01B0EC-1E546A-
276470-376045
01B0EC-1E547B-
277D8C-377045
8<SP≤12
01B0EC-1E5997-
275A64-376020
01B0EC-1E55D1-
276470-376045
01B0EC-1E55E2-
277D8C-377045
12<SP≤15
01B0EC-1E5D0E-
275A64-376020
01B0EC-1E5926-
276470-376045
01B0EC-1E5937-
277D8C-377045
15<SP≤ 17.5
01B0EC-1E5E64-
275A64-376020
01B0EC-1E5959-
276470-376045
01B0EC-1E596A-
277D8C-377045
17.5<SP≤20
01B0EC-1E5ECA-
275A64-376020
01B0EC-1E597B-
276470-376045
01B0EC-1E598C-
277D8C-377045
Model
AC048MNHDCH
Static Pressure(mmAq)
Option code for indoor unit
4≤SP≤5.2
01B0EC-1E5468-278CA0-377045
5.2<SP≤8
01B0EC-1E54AC-278CA0-377045
8<SP≤12
01B0EC-1E5913-278CA0-377045
12<SP≤15
01B0EC-1E5948-278CA0-377045
15<SP≤ 17.5
01B0EC-1E597B-278CA0-377045
17.5<SP≤20
01B0EC-1E59AE-278CA0-377045
Содержание AC***KNLDCH