14
MEMO
Drainpipe and drain hose installation
1. Check the leak test at the connection part of the flexible hose and the
distributing pipe (PVC).
1) Connect a general hose to the connection part of the flexible hose of the
indoor unit, and pour in some water.
2) After pouring some water, reassemble the rubber cap on the connection
part of a flexible hose of the indoor unit and tighten it with a band firmly to
prevent leakage.
3) Check the leak test at the part where the adhesive for the flexible hose and
the distributing pipe is used.
2. Check the condensed water drainage.
1) Pour about 2 liters of water into the indoor unit drain board as shown in the
picture.
2)
When the electric cable connection is completed
Turn the indoor unit and outdoor unit on.
Operate the Cool mode.
When the electric cable connection has not been completed
Remove the control box cover of the indoor unit.
Connect the power supply of 220V, 50Hz to L, N terminal.
Reassemble the control box cover and turn on the indoor unit.
3) Check whether the drain pump works correctly.
4) Check whether the drainage is performing correctly at the end of the drain pipe.
5) Check for leakage at the drain pipe and drain pipe connection part.
6) When leakage occurs, check whether the indoor unit is level and check the drain hose connection part, drainpipe
connection part and drain pump connection.
7) When the drainage check is completed and the condensed water remains on the drain board, remove the water.
Testing the drainage
Water leakage
check part
Hose
Installing DPM
▶
When installing DPM, you should set ‘DPM setting’ to the outdoor unit.
▶
If DPM model is not set, communication error may occur.
▶
While the outdoor unit is tracking the indoor unit for one minute after the power supply is turned on, the operation may
stop if the remote control reception signal of the installed indoor unit is different.
• The leak test should be performed for more than 24hours at least.
• Only in Cool mode, you can check the correct operation of the drain
pump.
• When the float switch is not detected due to insufficient water on the drain board, the drain pump will not work.
• If power supply is directly connected to L, N terminal, communication error message might appear.
• After completing the drainage check, turn the unit off and disconnect the power supply.
• Reassemble the control box cover.