3
.
Installing the Product
Confidential
48
English 8/2019. Rev 0.0
3.10.4
Fuse-Busbar Assembly
Three types of fuse-busbar assemblies must be assembled before installing them to the Battery Modules.
NOTICE
Rack Fuse Busbar Assembly is assembled at the installation location.
M12 X 16L screws are used to assemble the busbars and fuse.
The fastening torque should be 30 Nm (300 kgf/cm).
When assembling the fuse, make sure the “red indicator arm” on the fuse is facing the front of the
unit.
1.
Assemble the Rack fuse Bus-bar assembly.
Rack fuse bus-bar assembly is comprised of one “RACKFUSE BUSBAR_R_136S”, one “RACKFUSE BUSBAR_L_136S”, two
“SCREW M12 X 16”, one “FUSE COVER #1”, and one “FUSE”
Figure 3-30: Rack Fuse Busbar Assembly
Figure 3-31: Rack Fuse Busbar Assembly (Fuse Cover)
Содержание 136S
Страница 1: ...Confidential English 8 2019 Rev 0 0 LIB System for UPS Installation Manual 136S ...
Страница 4: ...Confidential English 8 2019 Rev 0 0 ...
Страница 10: ...Important Safety Instructions Confidential vi English 8 2019 Rev 0 0 ...
Страница 18: ...Confidential Table of Contents viii English 8 2019 Rev 0 0 ...
Страница 149: ...Confidential 3 Installing the Product English 8 2019 Rev 0 0 131 Figure 3 164 Cell Information ...
Страница 153: ...Confidential Memo ...
Страница 154: ...Confidential Memo ...
Страница 155: ...Confidential Memo ...
Страница 156: ...www SamsungSDI com ...