Solenoid valve
Input
Binary direct current signal
Nominal signal
6 V DC
12 V DC
24 V DC
Signal 0 (no pick-up) , DC signal at 25 °C
≤
1.2 V
≤
2.4 V
≤
4.7 V
Signal 1 (safe pick-up), DC signal at +80 °C
≥
5.4 V
≥
9.6 V
≥
18 V
Max. permissible signal
28 V
25 V
32 V
Coil rsistance R
at 20 °C
2909
Ω
5832
Ω
11714
Ω
Air consumption in steady state, K
= 0.14 m
/h
In addition to that of the positioner: "Off"
≤
60 l
/h; "On"
≤
10 l
/h
Closing time for
For rated travel and
signal pressure
range
Type 3277 Actuator cm
120
240
350
700
0.2 to 1 bar
≤
0.5 s
≤
1 s
≤
1.5 s
≤
4 s
0.4 to 2 bar
≤
2 s
≤
2.5 s
≤
8 s
0.6 to 3 bar
≤
1 s
≤
1.5 s
≤
5 s
Position transmitter
Instrinsically safe output current circuit
Output signal
Two-wire system 4 to 20 mA, reversible operating direction
Permissible load
U
12 V
R
=
20 mA
Power supply
Voltage range 12 to 45 V DC
Only with intrinsically safe current circuit
Characteristic
Output linear to input, deviation from characteristic
≤
1 %
Hysteresis
≤
0.6 %
Response span
≤
0.1 %
Power supply influence
≤
1 % when voltage changes within the specified limits
HF influence
≤
0.1 %, f = 150 MHz, 1 W transmitter power at a distance of 0.5 m
Load influence
≤
0.1 %
Permissible ambient temperature
20 to +70 °C
20 to ... See declaration of conformity
Ambient temperature influence
≤
0.4 % on lower measuring range limit,
≤
0.2 % on measuring span
Ripple of output signal
≤
0.3 %
Data refer to standard spring (15 mm travel with Type 3277 Actuator) and gain of 100
EB 8355-1 EN
9
Technical data
Содержание Type 3766
Страница 41: ...EB 8355 1 EN 41...
Страница 42: ...42 EB 8355 1 EN...
Страница 43: ...EB 8355 1 EN 43...
Страница 44: ...44 EB 8355 1 EN...
Страница 45: ...EB 8355 1 EN 45...
Страница 51: ...EB 8355 1 EN 51...